Performance Data
Table 6.
Unit air pressure drop – in. wg (I-P) (continued)
Fan/Inlet Size
Airflow Cfm Cooling Only
Fan/Inlet Size
Airflow Cfm Cooling Only
02SQ-10
165
550
950
1400
0.01
0.01
0.01
0.01
05SQ-14
320
1200
2100
3000
0.01
0.01
0.01
0.01
03SQ-06
60
200
350
500
0.01
0.06
0.19
0.40
06SQ-10
165
550
950
1400
0.01
0.01
0.01
0.01
03SQ-08
105
350
600
900
0.01
0.03
0.08
0.20
06SQ-12
240
750
1350
2000
0.01
0.01
0.01
0.01
03SQ-10
165
550
950
1400
0.01
0.01
0.02
0.05
06SQ-14
320
1200
2100
3000
0.01
0.01
0.01
0.01
03SQ-12
240
750
1350
2000
0.01
0.01
0.01
0.01
06SQ-16
420
1600
2800
4000
0.01
0.01
0.01
0.01
04SQ-08
105
350
600
900
0.01
0.03
0.08
0.20
07SQ-10
165
550
950
1400
0.01
0.01
0.01
0.01
04SQ-10
165
550
950
1400
0.01
0.01
0.02
0.05
07SQ-12
240
750
1350
2000
0.01
0.01
0.01
0.01
04SQ-12
240
750
1350
2000
0.01
0.01
0.01
0.01
07SQ-14
320
1200
2100
3000
0.01
0.01
0.01
0.01
07SQ-16
420
1600
2800
4000
0.01
0.01
0.01
0.01
Note: Unit pressure drops do not include hot water coil or attenuator pressure drops.
Table 7.
Coil air pressure drop – in. wg (I-P)
Fan Size
Airflow Cfm
1-Row HW (in. wg)
2-Row HW (in. wg)
02SQ
100
200
300
400
500
0.00
0.01
0.01
0.02
0.02
0.00
0.01
0.02
0.03
0.05
03SQ
04SQ
05SQ
250
500
750
1000
1250
1400
0.01
0.02
0.04
0.07
0.10
0.12
0.02
0.04
0.08
0.13
0.19
0.23
06SQ
07SQ
600
900
1200
1500
1800
2000
0.02
0.04
0.06
0.09
0.12
0.15
0.04
0.07
0.11
0.16
0.22
0.27
Note: HW Coil Only pressure drops do not include unit pressure drop.
VAV-PRC012-EN