Download Stepnet Panel Manual
Transcript
Mode Selection and General Setup Stepnet Panel Amplifier User Guide 5.7.4: Analog Command Input (STX Servo Mode Only) For more information, see Analog Command Input (STX Servo Mode Only) (p. 25). Click Analog Command to open the Analog Command screen. 5.7.4.1 5.7.4.2 5.7.4.3 Set the input options described below. Option Description Scaling Current mode: output current produced by +10 Vdc of input. Range: 0 to 10,000,000 A. Default: Peak Current value. Velocity mode: output velocity produced by +10 Vdc of input. Range: 0 to 100,000 rpm (mm/sec). Default: Maximum Velocity value. Position mode: position change (counts or mm) produced by +10 Vdc of input. Range: 0 to 1,000,000,000 counts. Default: 1 Revolution of a rotary motor or 1 pole pair distance for a linear motor. For more information, see Scaling (p. 25). Dead Band Sets dead band. Range: -10,000 to 10,000 mV. Default: 0. For more information, see Dead Band (p. 25). Invert Command Inverts polarity of amplifier output with respect to input signal. Offset (Current and Velocity modes only.) Used to offset input voltage error in an open loop system. Not recommended for use when the amplifier is part of a closed loop system. Range: -10,000 to 10,000 mV. Default: 0. For more information, see Offset (p. 26). Analog Input Filter Programmable input filter. Disabled by default. See “Low-Pass and Bi-Quad Filters” in the CME 2 User’s Guide. Click Close. 5.7.4.4 On the Main screen, click Save to Flash. 5.7.4.5 Proceed to Servo Mode Phase and Tune (p. 131). . 114 Copley Controls