Coopra Advanced Heating Technologies
Installation manual E40C
1.4.1. View mode
At the end of the menu structure, the view mode is shown.
The view mode is a reading only entry; no parameters can be changed in here.
The view mode is to enter directly.
Press the (+) button for at least 10 seconds. First upcoming is the water pressure P / u; in the Reading display on the
right hand segments is the actual water pressure in bar.
Press the Set/Reset button to next parameter.
To switch out of the view mode press the (-) button shortly or after timeout.
When the keys are untouched for 3 minutes, the system will switch out of the view mode automatically.
View mode
Single boiler
Status
P/u
‫ﬤ‬/u
1/u
2/u
3/u
4/u
5/u
6/u
7/u
9/u
A/u
d/u
Description
Actual water pressure left hand unit (in bar)
Setpoint temperature on flow sensor (in °C) (parameter C/r = 0)
Setpoint temperature on return or system sensor (in °C) (parameter C/r = 1)
Actual flow sensor temperature (in °C)
Actual return sensor temperature (in °C)
0÷10V control (in Volt)
Outdoor sensor temperature (in °C)
Combi-boiler internal tank or external storage cylinder temperature (in °C)
Flue gas sensor temperature (in °C)
Flame signal (in µA DC)
Last lock-out
Last blocking
Actual system sensor temperature (in °C) (parameter C/r=1)