Coopra Advanced Heating Technologies Installation manual E40C 1.4.1. View mode At the end of the menu structure, the view mode is shown. The view mode is a reading only entry; no parameters can be changed in here. The view mode is to enter directly. Press the (+) button for at least 10 seconds. First upcoming is the water pressure P / u; in the Reading display on the right hand segments is the actual water pressure in bar. Press the Set/Reset button to next parameter. To switch out of the view mode press the (-) button shortly or after timeout. When the keys are untouched for 3 minutes, the system will switch out of the view mode automatically. View mode Single boiler Status P/u ﬤ/u 1/u 2/u 3/u 4/u 5/u 6/u 7/u 9/u A/u d/u Description Actual water pressure left hand unit (in bar) Setpoint temperature on flow sensor (in °C) (parameter C/r = 0) Setpoint temperature on return or system sensor (in °C) (parameter C/r = 1) Actual flow sensor temperature (in °C) Actual return sensor temperature (in °C) 0÷10V control (in Volt) Outdoor sensor temperature (in °C) Combi-boiler internal tank or external storage cylinder temperature (in °C) Flue gas sensor temperature (in °C) Flame signal (in µA DC) Last lock-out Last blocking Actual system sensor temperature (in °C) (parameter C/r=1) 7