Download Emerson Liebert APS Installation manual

Transcript
Chapter 1 Installation
1
Chapter 1 Installation
This chapter introduces the installation of Liebert APM modular UPS, including preliminary checks, location,
positioning, cable connection and installation drawings.
1.1 Introduction
This chapter describes the requirements that must be taken into account when planning the positioning and cabling of
the UPS.
This chapter is a guide to general procedures and practices that should be observed by the installing engineer. The
particular conditions of each site will determine the applicability of such procedures.
Warning: professional installation required
1. Do not apply electrical power to the UPS equipment before being authorised to do so by the commissioning engineer.
2. The UPS shall be installed by a qualified engineer in accordance with the information contained in this manual. All the
equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation information.
Note: 3-phase, 5-wire input supply required
The standard UPS is suitable for connection to 3-phase, 5-wire (A, B, C, N, PE) TN, TT and IT AC power distribution systems
(IEC60364-3).
Warning: battery hazards
Special care should be taken when working with the batteries. When connected together, the battery terminal voltage will exceed
400Vdc and is potentially lethal.
Eye protection should be worn to prevent injury from accidental electrical arcs.
z
Remove rings, watches and all other metal objects.
z
Use only tools with insulated handles.
z
Wear rubber gloves.
z
If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in a container resistant to
z
sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin, the affected area should be washed immediately with water.
z
1.2 Preliminary Checks
Before installing the UPS, please carry out the following preliminary checks:
1. Visually examine the UPS rack for any transit damage, both internally and externally. Report any damage to the
shipper immediately.
2. Verify that the correct UPS is being installed. The UPS has an identification tag on the back of the front door
reporting the model, capacity and main parameters of the UPS.
1.3 Location
1.3.1 Power Distribution Room
The UPS is intended for indoor installation and should be located in an environment with clean air and with adequate
ventilation to keep the ambient temperature within the specified operating range.
The UPS is air-cooled with the aid of internal fans. Cold air enters the UPS through the ventilation grilles at the front
of the cabinet and hot air is released through the grilles at the back. Do not cover the ventilation openings.
Liebert APM Modular UPS User & Installation Manual