Download Schneider Electric Modbus Plus Network Bridge Multiplexer none Installation guide
Transcript
1.13 Bridging Modbus 1.13.1 How the Bridge Plus and Serial Devices Multiplexer Operates The BM85 Bridge Multiplexer device operates as a standard Modbus Plus node, receiving and passing tokens in the network’s address sequence. It provides four serial port connections to allow Modbus Plus nodes to communicate with serial devices. BM85 models are available for support of Modbus, RS232, and RS485 serial devices. 1.13.2 Modbus Configurations Each Modbus port can be configured to support a master device, slave device, or a network of up to 32 slave devices. Selection of ASCII or RTU mode, baud rate, parity, stop bits, link timeout value, and function code conversion is also configurable. Figure 22 illustrates four types of Modbus devices connected to a Bridge Multiplexer. MODBUS PLUS NETWORK (UP TO 64 NODES) CPU BM85 BRIDGE MULTIPLEXER 1 2 3 4 CPU CPU = MODBUS PORT P230 PROGRAMMING PANEL (MASTER) Figure 890 USE 100 00 IBM PC OR COMPATIBLE (MASTER) 22 Modbus Devices J478 MODBUS MODEM CPU (SLAVE) MODBUS NETWORK 1 ... 32 DEVICES Multiplexed Introducing to Modbus Plus the Modbus Plus Network 37