Download CPS US-480 Technical data
Transcript
This function will not respond when the inverter is in operation mode and a “FaultOperated” alarm interface will be indicated. (3) “3 Recover” menu, the manufacturer’s parameter default value can be restored when the inverter is not in operation mode. Otherwise, a “FaultOperated” will be prompted. (4) In “4 ClrErrRecd” menu, history information of the faults can be cleared. A confirmation is required to clear the records. GridV.Max(V) → 528 GridVmaxTripT (S) 1.80 GridV.Min(V) → 422 GridVminTripT (S) 1.80 →1 SysPara. 2 Restart 3 Recover 4 ClrErrRecd Pls Input Pwd **** Are You Sure? Are You Sure? PwdError Pls Input Again GridF.Min(Hz) → 59.30 GridFTripT (S) 0.08 Restarting... Success! Recovering.. FaultOperated Failure! Success! Are You Sure? FaultOperated Failure! Sucess! Figure 5-12 System parameter setup 50 Chapter 5 Human Machine Interface