Download WAGO Modular IO System INTERBUS S Technical data
Transcript
Ethernet/IP (Ethernet/Industrial Protocol) Object model • 183 7.3.2.8 TCP/IP Interface (F5 hex) Class Attribute ID Access Name Data type Description Default value 1 Get Revision UINT Revision of this object 1 (0x0001) 2 Get Max Instance UINT Max. number of instances 3 Get Num Instances UINT Number of the current instanced connections Instance 1 Attribute ID Access NV Name Data type Description Default value 1 Get V Status DWORD Interface state - Get V Configurat ion DWORD Capability Inferface flags for possible kinds of configuration 0x00000007 2 Set NV Configurat ion DWORD Control Specifies, how the device gets ist TCP/IP configuration after the first Power On 0x00000011 3 4 Get V Physical Link Object STRUCT of Path size UINT Size of the path 0x0004 UINT Number of 16 Bit words in the following path 0x0002 Padded EPATH Logical path, which points to the physical Link object 0x20 0xF6 0x24 0x01 IP Address UDINT IP address 0 Network Mask UDINT Net work mask 0 Gateway Address UDINT IP address of default gateway 0 Name Server UDINT IP address of the primary name of the server 0 Name Server 2 UDINT IP address of the secundary name of the server 0 Domain Name STRING Default Domain name “” Host Name STRING Device name local host Path Interface Configurat STRUCT of ion 5 6 Get Set NV NV Common Services Service code Service available Service Name Description yes Get_Attribute_All Supplies contents of all attributes yes yes Get_Attribute_Sing le Supplies contents of the appropriate attribute no yes Set_Attribute_Singl Modifies an attribute value e Class Instance 01 hex yes 0E hex 10 hex WAGO-I/O-SYSTEM 750 ETHERNET TCP/IP