Download SILENT KNIGHT 9800 Specifications
Transcript
Section 6 Compatible Reporting Formats This section lists all the reporting formats that are compatible with the 9800. Table 6-1 shows the formats that the 9800 can decode, handshake frequency format group which accommodates that format (see Section 5.5 for line card programming). Each line card can decode every format listed below, however, a line card can be programmed to prioritize the handshake order in which that line card will communicate. 6.1 Formats By Communication Group. Table 6-1 shows which formats fit under the general communication groups and the corresponding handshake frequency. Table 6-1: Formats compatible with the 9800 Communication Group Tone Burst DTMF 151018 Format Name Description Handshake Format Group SK 4+2 Sends a 4-digit account and a 2-digit alarm code up to 1400 Hz four rounds. Sescoa 3+1/Franklin 3+1 Sends a 3-digit account and a 1-digit alarm code up to 2300 Hz four rounds in a tone burst format. Each digit can be programmed from (0-9). Because there is no standard, this format reports in codes only. Radionics 3+1 Checksum Sends a 3-digit account and a 1-digit alarm code and a 1400 or 2300 Hz checksum. SK 3+1/3+1 Extended Sends a 3-digit account and a 1-digit alarm code up to 1400 or 2300 Hz four rounds (10-40pps). Each block of data (2 rounds). If a second block of data is sent, it will contain the extended information. The account number cannot have repetitive digits (333, 888, etc.). 4+1/4+1 Extended Sends a 4-digit account code and a 1-digit alarm code 4/1 1400 or up to four rounds in a pulse format (10-40pps). 4/1 2300 Hz Pulse 4+2 sends a 4-digit account code and a 2-digit alarm code. 1400 or 2300 Hz Ademco Contact ID Dual Tone Multiple Frequency. The data is decoded into English account information. Ademco Super Fast, Sends a 4-digit account code and a 2-digit alarm code up to 9 events per call. Acron Touch Tone Sends a 4-digit account code and a 1-digit alarm code. Will send a maximum of 8 events per call. Ademco Express Sends a 4-digit account code and a 2-digit alarm code with a checksum. DTMF 4+2 Sends a 4-digit account code and a 2-digit alarm code with a checksum. FBI 4+3+1 Sends a 4-digit account code, a 3-digit zone code and a 1-digit event code. 1400 or 2300 Hz Westec Sends a 4-digit account code, a 3-digit Dealer code followed by the event code. Westec 1400_2300 Hz 6-1