Download SILENT KNIGHT 9800 Specifications

Transcript
Section 6
Compatible Reporting Formats
This section lists all the reporting formats that are compatible with the 9800.
Table 6-1 shows the formats that the 9800 can decode, handshake frequency format group
which accommodates that format (see Section 5.5 for line card programming). Each line card
can decode every format listed below, however, a line card can be programmed to prioritize
the handshake order in which that line card will communicate.
6.1
Formats By Communication Group.
Table 6-1 shows which formats fit under the general communication groups and the
corresponding handshake frequency.
Table 6-1: Formats compatible with the 9800
Communication
Group
Tone Burst
DTMF
151018
Format Name
Description
Handshake
Format Group
SK 4+2
Sends a 4-digit account and a 2-digit alarm code up to 1400 Hz
four rounds.
Sescoa 3+1/Franklin 3+1
Sends a 3-digit account and a 1-digit alarm code up to 2300 Hz
four rounds in a tone burst format. Each digit can be
programmed from (0-9). Because there is no standard,
this format reports in codes only.
Radionics 3+1 Checksum
Sends a 3-digit account and a 1-digit alarm code and a 1400 or 2300 Hz
checksum.
SK 3+1/3+1 Extended
Sends a 3-digit account and a 1-digit alarm code up to 1400 or 2300 Hz
four rounds (10-40pps). Each block of data (2 rounds).
If a second block of data is sent, it will contain the
extended information. The account number cannot
have repetitive digits (333, 888, etc.).
4+1/4+1 Extended
Sends a 4-digit account code and a 1-digit alarm code 4/1 1400 or
up to four rounds in a pulse format (10-40pps).
4/1 2300 Hz
Pulse 4+2
sends a 4-digit account code and a 2-digit alarm code. 1400 or 2300 Hz
Ademco Contact ID
Dual Tone Multiple Frequency. The data is decoded
into English account information.
Ademco Super Fast,
Sends a 4-digit account code and a 2-digit alarm code
up to 9 events per call.
Acron Touch Tone
Sends a 4-digit account code and a 1-digit alarm code.
Will send a maximum of 8 events per call.
Ademco Express
Sends a 4-digit account code and a 2-digit alarm code
with a checksum.
DTMF 4+2
Sends a 4-digit account code and a 2-digit alarm code
with a checksum.
FBI 4+3+1
Sends a 4-digit account code, a 3-digit zone code and
a 1-digit event code.
1400 or 2300 Hz
Westec
Sends a 4-digit account code, a 3-digit Dealer code
followed by the event code.
Westec
1400_2300 Hz
6-1