Operating the PROFIBUS CP with STEP S7
Table 3-5
CALL SFC 58 ”WR_REC” (write data record)
STL
Explanation
REQ
IOID
:=M10.0
:=B#16#54
//
//
//
//
LADDR :=W#16#100
RECNUM :=B#16#3
//
RECORD :=P#DB45.DBX 0.0 BYTE 3 //
RET_VAL :=MW12
//
BUSY
:=M10.1
//
//
Table 3-6
Trigger bit for the job
Module base address of the PROFIBUS CP is in the
input area (PI)
Module base address of the PROFIBUS CP
Select data record 3
Data area for data record 3 − data in DB 45
Return value of block in memory word 12
SFC returns code: job active (1),
Job done (0)
DB 45
Parameter / Name
Type
0
Ctrl-Type
Byte
0: no change
1: allow change
1
Mode
Byte
New mode
2
PROFIBUS
address
Byte
New PROFIBUS address
(Relative)
Address
Comment
Notice
The module can then only be operated in the DP master mode if it was
configured in the hardware configuration as DP master.
If an invalid mode (>3) or an invalid PROFIBUS address (> HSA) is specified,
no change is made. SFC 58 does not, however, signal an error to the user
program.
Caution
The change is retained until power off/on on the station or until it is
reconfigured using data record 3.
After power off/on, the CP returns to the configured mode and PROFIBUS
address (default).
A−80
S7-CPs for PROFIBUS Configuring and Commissioning
Release 09/2011
C79000−G8976−C181−05