MOTORMASTER® V CONTROL INSTALLATION (48TJ024,028 UNITS) Install Field-Fabricated Wind Baflles -- Wind baflles must be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 21 for baflle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should be l/4-in, diameter and 5/8-in. long. Drill required screw holes for mounting baffles. FROM FUSE BLOCK 10 o---1 >- u ca 1.2 1.3 o o To avoid dmnage to the refligerant coils and electrical components, use lecommended screw sizes only. Use cme when &'illing holes. B 13B Install Motormaster V Controls -The Motormaster V (MMV) control is a motor speed control device which adjusts condenser fan motor speed in response to declining liquid lefrigerant pressure. A properly applied Motormaster V control extends the operating range of air-conditioning systems and permits operation at lower outdoor ambient temperatures. The minimum operate are: mnbient temperatures Unit 40 ooo o at which the unit will TO MOTOR(S) TEMPERATURE Standard o TO PRESSURE TRANSDUCER OPERATING Unit with Low Ambient 25 Kit Fig. 23 -- Motormaster LIMITS -- F° I Unit with I MMV -20 Control V Control Table 6 -- Motormaster V Control Package Usage To operate down to the ambient temperatures listed, Motormaster V controls (Fig. 23) must be added. Field-fabricated and installed wind baffles gue _dso required for _dl units (see Fig. 21). The Motormaster V control permits operation of the unit to an ambient temperature of-20 IF.The control regulates the speed of 3-phase fan motors that gue compatible with the control. These motors me factory installed. ITEM DESCRIPTION 48TJ024,028 UNIT V control per instructions CRLOWAMB015A00 460 VOLTAGE 575 CR LOWAMB016A00 Table 7 -- Applicable See Table 6 for the Motormaster V control accessory package usage. Table 7 shows applicable voltages and motors. Replacement of motor or fan blade IS NOT REQUIRED ON CURRENT PRODUCTION UNITS since the control is compatible with the factory-installed fan motors. Only field wiring control is required. Inst_dl the Motormaster with accessory. I 208/230 VOLTAGE 208/230-3-60 480-3-60 575-3-60 supplied 16 CRLOWAMB017A00 Voltages and Motors COMPATIBLE MOTOR HD52AK654 HD52AK654 HD52GE576