Property <InterfaceOptions> Description This element contains the following options for Modbus channels attached to the RS-232 or RS-485 serial ports on the SmartServer (<UCPTchannelType> is CT_RS485_MASTER or CT_RS232 _MASTER): • • • • <UCPTspeed>. The baud rate at which the SmartServer communicates with the Modbus devices on the channel. The default value is MS_9600. This property may be one of the following values: MS_110 MS_300 MS_600 MS_1200 MS_2400 MS_4800 MS_9600 MS_19200 MS_38400 MS_57600 MS_115200 <UCPTsize>. The data bit size for messages sent over the Modbus network. A data bit is a group of 5 to 8 bits that represents a single character of data for transmission over the network. Data bits are preceded by a start bit, and they are followed by an optional parity bit and one or more stop bits. The default value is CS_8. This property may be one of the following values: CS_5 CS_6 CS_7 CS_8 <UCPTparity>. The parity bit size for messages sent over the Modbus network. A parity bit is an extra bit used to check for errors in groups of data bits transferred between devices. The default parity size is P_NONE. This property may be one of the following values: P_NONE P_ODD P_EVEN <UCPTstopBits>. The number of stop bits used on the Modbus network. The default value is SB_1. This property may be one of the following values: SB_1 SB_2 This property is not available for TCP/IP Modbus channels. i.LON SmartServer 2.0 Programmer’s Reference 15-4