Download ETIC 2230 User`s guide
Transcript
Configuration 4.7 IP<>RS gateway menu That menu allows to configure the IP to asynchronous RS232-RS485 gateway included in the XSLAN. 4.7.1 Modbus menu The ETIC modbus gateway is made to link modbus devices connected to its serial interface to TCP modbus devices connected to the ethernet TCP/IP network. 4.7.1.1 Definitions A TCP Modbus client device is a device connected to the ethernet TCP/IP network and able to send a modbus request to a modbus TCP server which is in charge of answering; A TCP modbus client is equivalent to a master. A TCP Modbus server device is a device connected to the ethernet TCP/IP network and able to answer to a modbus request received from a TCP modbus client device. A TCP modbus server is equivalent to a slave. A TCP modbus server can answer to any client of the Ethernet TCP/IP network. 4.7.1.2 ETIC modbus gateway capabilities The ETIC modbus gateway can be configured either to link serial slaves to several TCP modbus clients devices connected to the ethernet network; in that case, select the modbus client gateway, or to connect a serial master to several TCP modbus servers devices connected to the ethernet network; in that case, select the modbus server gateway. XSLAN shdsl switch User’s guide ref 9014709-01 Page 33