Download USER`S MANUAL - HTA Instrumentation Pvt Ltd
Transcript
USER’S MANUAL Manual for PID CONTROLLER PV OUT1 PV OUT2 SV AT AL 1 SV AL 2 PRO OUT1 OUT2 AT AL 1 AL 2 AL 3 MAN PRO % OUT1 0 20 40 60 80 100 SET A/M SET EQ-TB100 EQ-100 EQ-900 EQ-900 NQA QSR JAS-ANZ Registration No. S I 9 1 0 7 9 9 I N HALLMARK OF EXCELLENCE ISO 9001-2000 C E RT I F I E D HTA INSTRUMENTATION PVT LTD. 73, Ramachandra Agrahara, Near T. R. Mills, Chamarajpet, Bangalore-18. TEL: 080-26749750, 26759253 FAX: 080-26740681, E-mail: [email protected], Web: www.htaipl.com - EXTERNAL DIMENSION & PANEL CUTOUT [Unit : mm] 50 14 +0.5 44.5 0 OUT1 PV EQ-100 +0.5 44.5 0 60 OUT2 AT AL 1 SV AL 2 70 50 PRO SET EQ-TB100 65 96 14 80 +0.5 90.5 0 PV +0.5 90.5 0 SV EQ-900 OUT1 OUT2 AT 116 96 AL 1 AL 2 AL 3 MAN PRO % OUT1 0 20 40 60 80 100 SET A/M 111 EQ-900 - PARTS DESCRIPTION EQ-100 8 OUT1 PV 9 OUT2 1 AT AL 1 SV AL 2 2 PRO SET 10 11 12 15 EQ-100 3 SYMBOL 5 6 7 NAME PV 1 Measured value (PV) display SV 2 Setting value (SV) display SET 3 Set Key A/M 4 5 FUNCTION Display PV or various parameter Symbols (Red) Display SV or various parameter set values (Green) Used for parameter calling up & set value registration Auto/Manual Key Switches between Auto (PID) output mode & Manual Output Shift Key Shift digits when settings are changed 6 Down Key Decrease numbers (*Only for programmable controller) (*Program Hold) 7 Up Key (*Program Run) Increase Numbers (*Only for programmable controller) 2 EQ-900 8 9 10 11 12 13 14 15 PV 1 SV 2 OUT1 OUT2 AT 16 AL 1 AL 2 AL 3 MAN PRO % OUT1 0 20 40 60 80 100 SET A/M EQ-900 3 SYMBOL 4 5 6 7 NAME FUNCTION OUT1 Lamp Light when OUT1 is on (Green) OUT2 Lamp Lights when OUT2 is on (Green) OUT1 8 OUT2 9 AT 10 Auto-tuning Lamp Lights when Auto-tuning is activated (Orange) AL1 11 Alarm-1 Lamp Lights when Alarm 1 is activated (Red) AL2 12 Alarm-2 Lamp Lights when Alarm 2 is activated (Red) AL3 13 Alarm-3 Lamp Lights when Alarm 3 is activated (Red) MAN 14 Manual O/P Lamp Lights when Manual Output is activated (Orange) PRO 15 Program Running Flashes when program running Lamp (Only for programmable controller) OUT% 16 Output% BarGraph Display Output% is displayed on 10-dot LEDS - TERMINAL ARRANGEMENT EQ-100 A. Power Supply 1 AC 85~265V DC 15~50V (Option) 6 11 2 12 3 13 4 14 5 3 7 8 9 10 H. CT Input 11 CT 12 C. Input B. Control Output OUT1 + + 2 + + 5 – 3 – – – B – 10 • 8 8 I. SET2.1=1 g To display AL3 9 +9 II. SET4.1=1 g To display ALD3 10 – 10 A III. ALD3=9 g Open RAMP option IV. Then, AL3 will not display. It was replaced by RAMP. RAMP D. Alarm (Option) OUT1 (1Ø Zero Cross Control) OUT1 (Proportional Motor Valve Control) 11 G1 (Use OUT1 & OUT2) (Motor Valve Control) AL1 AL2 2 13 11 3 14 12 12 CLOSE 13 G2 13 OPEN 14 K2 14 COM E. Transmission F. Communication TRS + RS232 • SOAK : I. ALD1 / ALD2=19 g To use Sock Timer. II. AL1 / AL2 will display as below: TTL RS485 11 RD 11 Dx– 11 RD – 12 SD 12 SG 13 Dx+ 00.00 Range : 00.00 ~ 99.99(°C/ min) (If RAMP is not used please set ALD3 to 0) AL1 11 12 K1 RAMP & SOAK 7 • RAMP : 8 9 APPLICATIONS 7 B Relay SSR mA / V 4 TC / mV RTD mA / V + 7 OUT2 Relay SSR mA / V - 11 12 SD 12 SG 13 AL1 Range : 00.00 ~ 99.59 (Hour. Minute) 00.00 • Example : EQ-900 SV=100°C RAMP=10.00 (/min) ; AL1=00.10 min ; PV=25°C °C Time on A. Power Supply AC 85~265V DC 15~50V (Option) H. CT Input 14 CT 15 E. Transmission 1 21 31 11 2 22 32 12 3 23 33 13 4 24 34 14 5 25 35 15 6 26 36 16 7 27 37 17 F. Remote Remote SV + 8 28 38 18 9 29 39 19 10 30 40 20 Time up AL1 on if PV > = SV(100°C) TRS + 39 100°C – 40 AL1 00.10 00.01 00.10 Sock Timer counts 1sec. SV=SV+RAMP 14 PV=25°C SV=PV (When start RAMP function) – 15 t Power on 4 5 seconds (Start RAMP function) 21 B. Control Output - CALIBRATION SET 2.2 = 1 OUT1 To display ANL1 & ANH1 Relay SSR mA / V NO 8 NC + + – 10 COM at INPUT Level OUT2 Return User Level to view the changing of PV – Relay SSR mA / V 6 + + 7 – mA / V + 17 18 33 G2 33 RG2 19 39 35 TG1 – 20 40 PROT RTD TC / mV 17 17 18 18 19 +19 20 – 20 B 31 RG1 31 G1 9 ANL1=0 ANH1=5000 LSPL=0 USPL=5000 C. Input OUT1 OUT1 (1Ø Zero (3Ø Zero Cross Control) Cross Control) B D. Alarm 37 TG2 39 AL1 – AL2 AL3 3 NC NC 11 6 4 NO NO 12 7 5 COM COM 40 OUT1 (Proportional Motor Valve Control) Inputs 4mA OUT1 (1Ø Phase Angle Control) 6 7 CLOSE PROT OUT1 (3Ø Phase Angle Control) 31 G1 31 G1 32 K1 32 K1 RS232 Adjusts "ANL1" until PV Display = 0 8 OPEN 9 Inputs 20mA 10 33 G2 33 G2 34 K2 34 K2 35 G3 36 K3 35 COM 36 PROT 13 G. Communication RS485 TTL RD 14 Dx– 14 RD 14 SD 15 Dx+ 15 SG SG 16 16 (Remote SV) RS232 SD 15 RS485 RD 31 Dx 31 SD 32 Dx+ 32 SG 33 39 Adjusts "ANH1" until PV Display = 5000 Inputs 4mA to CHECK LOW Inputs 20mA to CHECK HIGH 40 - OPERATIONS 1. Power ON : Controller will display as following PV PV PV SV SV SV OUT1 OUT2 AT AL 1 AL 2 AL 3 MAN PRO %% OUT1 0 20 40 60 80 OK ? YES Set the range you want : 20 AT AL 1 AL 2 AL 3 MAN PRO OUT1 %% 0 20 40 60 80 PV SV OUT2 AT AL 1 AL 2 AL 3 MAN PRO OUT1 %% OUT1 100 0 20 40 60 80 AT AL 1 AL 2 AL 3 20 40 60 80 MAN PRO %% 100 0 SET A/M Display input type OUT2 OUT1 100 SET A/M Display Range (0.0~400.0) Read for use 2. Change the Set Value (SV) : Change SV from 0.0 to 100.0 PV PV PV SV SV SV OUT2 AT AL 1 AL 2 AL 3 20 40 60 80 MAN PRO %% OUT1 Ex : Low = -20.0 ; High = 50.0 SET : LSPL = -20.0 ; USPL = 50.0 ; DP : 000.0 OUT2 OUT1 SET A/M Light all LEDs & all 7 segment displays OUT1 LOW = LSPL ; HIGH = USPL OUT1 100 SET A/M NO PROT 0 100 SET A/M Press Key The SV number started to flash. The flashing digit indicates which digit can be set. OUT1 OUT2 AT AL 1 AL 2 AL 3 20 40 60 80 MAN PRO OUT1 %% OUT1 0 PV SV OUT2 AT AL 1 AL 2 AL 3 20 40 60 80 0 SET A/M MAN PRO %% OUT1 100 100 SET A/M Press Key To select the hundreds digit. Press Key To change the number to 1. 5 OUT1 OUT2 AT AL 1 AL 2 AL 3 20 40 60 80 MAN PRO %% OUT1 0 100 SET A/M Press SET Key To store the new set value. 3. Auto-tuning (AT) : Use AT function to automatically calculate and set the optimize PID value for your system. PV PV PV SV SV SV OUT1 OUT2 AT AL 1 AL 2 AL 3 20 40 60 80 MAN PRO OUT1 %% OUT1 0 OUT2 AT AL 1 AL 2 AL 3 20 40 60 80 MAN 0 SET A/M PRO OUT1 %% OUT1 100 Press SET Key To display Parameter AT. AT AL 1 AL 2 AL 3 20 40 60 80 MAN PRO OUT1 %% OUT2 AT AL 1 AL 2 AL 3 20 40 60 80 MAN 0 100 SET A/M Press SET Key Start Auto-tuning process (AT lamp will be lighted on) Press Key Change AT to "YES" Change AL 1 value to "5.0" (AL 1 active, if PV exceeds SV over 5.0) PV SV OUT1 PV SV OUT2 AT AL 1 AL 2 AL 3 20 40 60 80 MAN PRO OUT1 %% OUT1 0 AT AL 1 AL 2 AL 3 20 40 60 80 SET A/M MAN PRO OUT1 %% 0 SV OUT2 AT AL 1 AL 2 AL 3 20 40 60 80 MAN PRO OUT1 %% OUT1 100 0 SET A/M Press SET Key To display Parameter AL1. R1 R2 R5 R3 AT AL 1 AL 2 AL 3 20 40 60 80 MAN PRO %% 0 SET A/M Press Key To change AL1 value OUT2 OUT1 100 100 SET A/M 9 ..... 6 6 ... 9 10 Modification of Input “TC” “RTD” (on PC board) If the controller needs modification from TC or RTD type, please make PAD short on PC board back as following diagram and changing input selection. On the contrary, modify from RTD to TC or mV, make PAD open. 96×96, 48×96, 96×48 (PC Board) Press SET Key Store the new value of AL1 Press Key Increase AL1 value S1 S2 S4 S3 S5 - PV SV OUT2 OUT1 100 R4 10 4. Change the Alarm Value : PV BACK PRO %% OUT1 100 SET A/M Press Key To change AT setting. FRONT SV OUT2 0 SET A/M 48×48 (PC Board) PV OUT1 100 48×48 (PC Board) RTD : TC or mV : * There are total 16 alarm mode types, referenced as below : * To change Alarm mode, Press SET + Key 5 seconds to enter Level 3 (Input Level) and then change the value of ALD1 / ALD2 / ALD3 PAD SHORT PAD OPEN 5. Alarm Mode Type (Referenced for ALD1 / ALD2 / ALD3) : (q : SV r : Alarm set value) 01 Deviation High Alarm with Hold Action* OFF ON HIGH Band Alarm PV 04 14 Deviation High Alarm 11 02 OFF ON HIGH PV Deviation Low Alarm with Hold Action* HIGH 05 03 ON OFF HIGH 15 PV OFF ON HIGH OFF HIGH PV Process High Alarm with Hold Action* OFF Low ON HIGH PV Segment End Alarm (Only for Programmable Controller) (1) ALD1~3, set 07 07 (2) ALD1~3=Alarm Segment (3) ALT1~3 defines as follows: =Flicker Alarm 0 =Continued Alarm 99.59 =Alarm ON Time others OFF Low ON HIGH 17 PV 06 OFF HIGH ON LOW ON LOW OFF ON HIGH PV 6 RTD : PAD SHORT TC or mV : PAD OPEN OFF AL 08 PV Normal Failed OFF ON AL System Failed Alarm* (OFF) 18 PV Normal Failed OFF ON Deviation High/Low Alarm 13 48×48 (PC Board) System Failed Alarm* (ON) Process Low Alarm 16 PV OFF HIGH ON LOW 11 12 13 14 15 16 17 18 19 20 Program Run Alarm (Only for Programmable Controller) Run Stop ON PV Process Low Alarm with Hold Action* Deviation High/Low Alarm with Hold Action* ON LOW ON Process High Alarm Deviation Low Alarm 12 OFF LOW 09 Heater Break Alarm (HBA) 00 10 No Alarm 6 AL - 7 8 9 10 Modification of output “Relay” “SSR” “4~20mA” If just needs to change a module at the same position & modify parameter CYT1 in LEVEL 2. 19 *Hold Action: When Hold action is ON, the alarm action is suppressed at start-up until the measured value (PV) enters the non-alarm range. *System Failed: It means that the controller display error message with one of following : "UUU1 or "NNN1 or "CJCE" - Alarm Alarm Time (ALT1 / ALT2 / ALT3) ALT1=0 ALT1=99.59 ALT1=00.01~99.58 Flicker Alarm Continued Alarm Alarm on delay time - PARAMETER LIST Levels Diagram - SETA Level 1 (User Level) *SETA is in Level 3 (Input Level) Press SET Key+ Press SET Key 5 seconds Level 2 Level 3 (Input Level) Press SET (PID Level) Key 5 seconds If SETA_1=1, AL1 relay will be action reversely If SETA_2=1, AL2 relay will be action reversely If SETA_3=1, AL3 relay will be action reversely If SETA_4=0, Program Run Alarm If SETA_4=1, Program End Alarm } Press SET Key+ *The controller returns to Level 1 if there is no key operation within 60 seconds. Only available for } programmable controller * In any Level, press A/M key twice will return to Level 1. Press SET Key+ - Modify Input Type : Linear Input (mA / V) - 5 seconds LEVEL 1 (User Level) Process Value Set Value Set 4~20mA (INP1=AN5) : (R3 use 100W , R5 use 2.4W , S3 & S5 SHORT) 0 ~ 1V (INP1=AN4) : (R1 use 2KW , R4 use 100W , S1 & S4 SHORT) 0 ~ 5V (INP1=AN4) : (R2 use 10KW , R4 use 100W , S2 & S4 SHORT) 1 ~ 5V (INP1=AN5) : (R2 use 10KW , R4 use 100W , S2 & S4 SHORT) 0 ~ 10V (INP1=AN4) : (R3 use 22KW , R4 use 100W , S3 & S4 SHORT) 2 ~ 10V (INP1=AN5) : (R3 use 22KW , R4 use 100W , S3 & S4 SHORT) Output Limit Set Auto-tuning Set Alarm 1 set value Heater current display HBA set value Set ( ( Set Alarm 2 set value Set Alarm 3 set value Set 18 5 seconds 5 seconds Level 4 (SET Level) 0~20mA (INP1=AN4) : (R3 use 100W , R5 use 2.4W , S3 & S5 SHORT) Press SET Key+ LCK=1111 When "b" contact (normal close) is needed • EQ-100, EQ- 900 Hardware : 5 seconds 7 * It will show, when HBA function enable • Description of operation - LEVEL 2 (PID LEVEL) Set Set Proportional band 1 (for output 1) Range : 0.01~200.0% ON/OFF control if set to 0 (0.0) Integral time 1 (For output 1) Range : 0~3600 seconds PD control if set to 0 Derivative time 1 (For output 1) Range : 0~900 seconds PI control if set to 0 Reserved Reserved Auto tuning offset value Range : 0~USPL Output 1 cycle time Range : 0~150 seconds Relay O/P : 10 Voltage pulse O/P: 1, mA O/P: 0 Hysteresis for output 1 ON/OFF control Range : 0~1000 Proportional 2 (For output 2) The same with P1 Set Set Set Set Display if output2 is provided Set Set Set Set Set : : : A program consists of some steps. The status with changing SV. The status with fixed SV. • Operating (RUN) : Start program procedure ' PRO LED in panel start flicking. (HOLD) : Suspend program procedure ' PRO LED in panel will stop +SET (JUMP) : Jump to previous segment. +SET (RESET) : Reset program procedure ' PRO LED in panel will off. flicker but still light on. II. Alarm Function ALD1 = “07”(Segment end alarm) Derivative time 2 (For output 2) The same with I1 AL1 = “2”(It means when segment 2 end,AL1 will act) Derivative time 2 (For output 2) The same with D1 * In this case ' when program proceeds to segment 2 end ' the relay of AL1 will be on 10 seconds. Output 2 cycle time The same with CYT1 ALT1 = “00:10”(Relay on time is 10 seconds). Set Display If P2=0.0 Pattern Ramp status Soak status I. "KEY" function (no changing parameter) Set Display If P1=0.0 1. There are 2 patterns can be used ' each pattern contains 8 segments. 2. Terminologies Hysteresis for output 2 ON/OFF control The same with HYS1 Control gap 1 (For output 1) Set point of output 1 (Heating side) =SV -GAP1 III. END function : The Controller doesn’t have END order, so if program procedure is less than 8 segments, please set the last segment’s OUT to “0”. Program will end in this segment. Otherwise ' it will proceed 8 or 16 segments. IV. Linking Function : PTN = 1 proceed pattern 1 ' contains 8 segments. Control gap 2 (For output 2) Set point of output 2 (Cooling side) =SV +GAP2 Set PTN = 2 proceed pattern 2 ' contains 8 segments. PTN = 0 linking proceed pattern 1 and 2 totally 16 segments. Function lock (Please set PTN1 and PTN2 at first ' and then set PTN to 0) Return to "P1" V. Other function (* refer to LEVEL 4) Levels Entering Available LCK Level 1 (User) Level 2 (PID) Level 3 (Input) Parameters which can be changed SET 8_2=1 Enable power failure function. All parameters (Factory set value) All parameters (When power shut down and on again ' the controller will start from the segment which is near PV) All parameters except level 3 SET 8_3=0 Program starts from 0. Parameters in level 1 SET 8_3=1 Program starts from PV. "SV" and "LCK" Only "LCK" 8 SET 8_1=1 Program repeats. SET 8_2=0 No power failure function. SET 9_2=0 Timer Unit = “Hour : Minute” SET 9_2=1 Timer Unit = “Minute : Second” 17 - Program Level (Only displayed in programmable controller) - ERROR DISPLAYS • Description of parameters IN1E : Input 1 Error Check whether input loop is opened or wiring incorrect. LEVEL 1 CJCE : Cold Junction Compensation Failed Set Program Pattern Range : 0~2 Set Check whether the input value is correct or not. Set time for Seg.5 Set NNN1 : PV is below LSPL Set Program countdown display Range : 0~99 hour 59 min Set Check whether the input value is correct or not. Output Limit of Seg.5 ADCF : A/D Convert Failed Set Setting value of Seg.1 Range : LSPL~USPL Controller needs to be repaired. Setting value of Seg.6 Set RAMF : RAM Failed Controller needs to be repaired. Set Set time for Seg.1 Range : 0~99hour 59min Set UUU1 : PV is above USPL Set Program Segment display (Pattern _ Segment ) Set Check the compensation diode outside controller. Setting value of Seg.5 Output Limit of Seg.1 Range : 0~100% If OUT=0 program will end. Set time for Seg.6 - Set LEVEL 3 (Input Level) Output Limit of Seg.6 Set Setting value of Seg.2 Input type selection Set Setting value of Seg.7 Set Set Set time for Seg.2 Set Set time for Seg.7 Set Set Set Output Limit of Seg.2 Output Limit of Seg.7 Set Setting value of Seg.8 Set Set Set time for Seg.8 Set Output Limit of Seg.8 Set Set Output Limit of Seg.3 Set Set Setting value of Seg.4 Return LEVEL 1 Set Analog input high limit calibration (Used for mA and V input) Range: 0~9999 Decimal point position (Available for mA & V input) 0000, 000.0, 00.00, 0.000 Lower Set-Point Limit Scaling Low Limit Upper Set-Point Limit Scaling High Limit Remote input low limit calibration Range: –1999~9999 Remote input high limit calibration Range: 0~9999 Alarm Mode of AL1 Range: 00.19 Refer to "Alarm Mode Type" Set Set Set time for Seg.3 Range: –1999~9999 Set Set Setting value of Seg.3 Analog input low limit calibration (Used for mA & V input) Set Set Set time for Seg.4 Range: 0~99 Min. 59 Secs. 0=Flicker Alarm 99:59=Continued Others=On delay time (If ALD=07, ALT means alarm on time) Alarm Time of AL1 Set Set Output Limit of Seg.4 16 9 Please don't operate SET 8_4, otherwise the controller's process will be in confusion. Alarm Mode of AL2 The same with ALD1 Alarm Time of AL2 The same with ALT1 Alarm Mode of AL3 The same with ALD1 Alarm Time of AL3 The same with ALT1 PV Hysteresis of all Alarm Range: 0~1000 SV Output 1 low limit Calibration (Used for mA and V output) Range: 0~9999 Output 1 high limit calibration (Used for mA and V output) Range: 0~9999 Output 2 low limit calibration (Used for mA and V output) The same with CLO1 Output 2 high limit calibration (Used for mA and V output) The same with CHO1 Retransmission low limit calibration The same with CLO1 Set Set If SET8.4 is set to “1”, the controller will enter into “Single Display” mode, the PV LED will not display any values. The SV LED will display both the parameter value and the setting value alternately as shown in the diagram below. Set Displayed alternately EMPTY Set Set Set Set Set To rectify the problem please press the SHIFT KEY (v) and change the setting value to “0000”. • Remote SV Type Selection INP2=0 None INP2=1 10~50mV / 4~20mA / 1~5V / 2~10V Set INP2=2 0~50mV / 0~20mA / 0~5V / 0~10V INP2=4 CT input ± Remote SV function is not available for programmable controller Set Retransmission high limit calibration The same with CHO1 Set Full run time of proportional motor (Used for proportional motor valve control output) Set Used for programmable controller to wait continued operation Set Set Range: 5~200 seconds 0=Not wait Others=Wait value Communication Protocol Selection MODBUS RTU / MODBUS ASCII / TAIE Communication Bits Configuration O_81/O_82/E_81/E_82 Set • Output Mode Selection (Use OUTY) OUTY=0 OUTY=1 OUTY=2 OUTY=3 Single output (OUT1) Dual output (OUT1 / OUT2) Reserved 3 wire proportional motor valve control OUTY=4 1 y Phase angle control (1ySCR) OUTY=5 3 y Phase angle control (3ySCR) • Modify caution If change parameter “BAUD”, “BITS”, “RUCY”, “OUTY” the power must be reset Set 10 15 Special functions (Use SET8 / SET9 / SET0) 8_ 1 8_ 2 8_ 3 8_ 4 0 1 0 1 0 1 0 : : : : : : : SET 8 Program not repeat Program repeat No power failure option With power failure option Program starts from 0 Program starts from PV Reserved (Don’t change it) ID number Range: 0~255 Baudrate 2400/4800/9600/19200/ 38400/ bps SV compensation Range: –1000~1000 PV compensation Range: –100.0~500.0 Unit of PV & SV C (°C) / F (°F) /A (Analog) PV Filter PV will response faster if PVFT is smaller. Set Remark Set Only available for programmable controller Set Set Set Remark SET 9 9_ 1 0 : Reserved (Don’t change it) 9_ 2 0 : Timer Unit = “Hour : Minute” 1 : Timer Unit = “Minute : Second” 9_ 3 Reserved Only available for programmable controller Set 0 : Disable transmission Control mode Heat / Cool Control algorithm PID / Fuzzy Frequency 50 / 60HZ Set Used for transmission output 1 : SV Transmission 9_ 4 Set 0 : Disable transmission Set 1 : PV Transmission Set Return to "INP1" Remark SET 0 0_ 1 0 : TTL Communication (Slave) 1 : TTL Communication (Master) 0_ 2 INPUT TYPE TABLE Used for TTL communication Type 0 : Hide parameter “RATE” 1 : Display parameter “RATE” 0_ 3 0 : Disable Remote SV function 0_ 4 1 : Enable Remote SV function 0 : use output relay “b” contact when motor valve closed 1 : use output relay “a” contact when motor valve closed 14 K AL3 will be replaced by “RATE” Used for Remote SV function Used for 3 wire proportional motor valve control J TC - R S B E N T W PLII U L K1 K4 J1 J4 R1 S1 B1 E1 N1 T1 W1 PL1 U1 L1 Range 0.0~200.0°C (392.0°F) 0~800°C (1472°F) 0.0~200.0°C (392.0°F) 0~800°C (1472°F) 0~1600°C (2912°F) 0~1600°C (2912°F) 0~1820°C (3308°F) 0~800°C (1472°F) 0~1200°C (2192°F) –199.9~400.0°C (752.0°F) 0~2000°C (3632°F) 0~1300°C (2372°F) –199.9~600.0°C (999.9°F) 0~400°C (752°F) Type Range K2 K5 J2 J5 R2 S2 0.0~400.0°C (752.0°F) 0~1000°C (1832°F) 0.0~400.0°C (752.0°F) 0~1000°C (1832°F) 0~1769°C (3216°F) 0~1769°C (3216°F) E2 N2 T2 W2 PL2 U2 L2 0~900°C (1652°F) 0~1300°C (2372°F) –199.9~200.0°C (392.0°F) 0~2320°C (4208°F) 0~1390°C (2534°F) –199.9~200.0°C (392.0°F) 0~800°C (1472°F) 11 Type Range K3 K6 J3 J6 0~600°C (1112°F) 0~1200°C (2192°F) 0~600.0°C (1112°F) 0~1200°C (2192°F) T3 0.0~350.0°C (662.0°F) U3 0.0~400.0°C (752.0°F) INPUT TYPE TABLE RTD Type JPT 100 PT 100 JPT 50 JP1 JP4 DP1 DP4 JP.1 JP.4 Range –199.9~600.0°C (999.9°F) 0~200°C (392°F) –199.9~600.0°C (999.9°F) 0~200°C (392°F) –199.9~600.0°C (999.9°F) 0~200°C (392°F) Range Type JP2 JP5 DP2 DP5 JP.2 JP.5 –199.9~400.0°C (752.0°F) 0~400°C (752°F) –199.9~400.0°C (752.0°F) 0~400°C (752°F) –199.9~400.0°C (752.0°F) 0~400°C (752°F) JP3 JP6 DP3 DP6 JP.3 JP.6 How to Hide Parameters (Use SET1~SET7) Range –199.9~200.0°C (392.0°F) 0~600°C (1112°F) –199.9~200.0°C (392.0°F) 0~600°C (1112°F) –199.9~200.0°C (392.0°F) 0~600°C (1112°F) 0 : Hide this Parameter 1 : Display this Parameter PV SV SET SET SET SET Range Type LINEAR - Type AN1 –10~10mV AN2 0~10mV AN3 0~20mV AN4 0~50mV An5 10~50mV –1999~9999 or –199.9~999.9 or –19.99~99.99 or –1.999~9.999 *For the description of Level 1 Parameters, please refer with page 17. *For the description of Level 3 Parameters, please refer with page 20. SET 1_1 - LEVEL 4 (SET Level) To enter level 4. set LCK to "1111 and then press SET key + Shift (v ) key 5 seconds. Press SET Key Display / Hiding Parameters SET SET Special Functions SET SET Remote SV Output Mode Setting Selection Display / Hiding , Level Level 3 , Level 3 1_3 Level 1 5_3 1_4 Level 1 5_4 2_1 Level 1 6_1 Level 3 Level 3 6_2 Level 3 Level 3 6_3 Level 3 Level 3 6_4 Level 3 3_1 Level 3 7_1 Level 3 3_2 Level 3 7_2 Level 3 3_3 Level 3 7_3 Level 3 3_4 Level 3 7_4 Level 3 4_1 Level 3 4_2 Level 3 4_3 Level 3 2_3 4_4 12 Level SET Level 1 5_1 Level 1 5_2 2_4 SET Display / Hiding 1_2 2_2 Press SET Key 1_1 1_2 1_3 1_4 , , , , , , Level 3 13 , , , Level 3 , , , , Level 3