Siemens SIMATIC TIWAY 1 User manual Download

Transcript
4.9.4
Configuration Primitive – Code 03
Primitive 03 allows the Primary to identify the types of devices that exist on the network.
For example, a Primitive 03 response from a TI525 P/C is different from a 5TI P/C response.
Request: LLLL 03
Response: LLLL 03 HH DDDD EEEE FFFF GGGG IIII JJJJ KKKK KKKK
Symbol
Value
Definition
HH
Attached device operational status
DDDD
Device type
0000
SIMATIC 5TI
0020
SIMATIC TI520
002C
SIMATIC TI520C, PPX:525–1102
0030
SIMATIC TI530
003C
PPX:525–1104, PPX:525–1208, PPX:525–1212,
SIMATIC TI530C, TI535
0040
SIMATIC TI540
0050
SIMATIC TI550
0060
SIMATIC TI560
0065
SIMATIC TI565
007E
SIMATIC UNILINK Host Adapter
0080
SIMATIC PM550
0081
SIMATIC PM551
0100
SIMATIC UNILINK Secondary Adapter
0200
IT–111/121 Intelligent Tank Transmitter
0204
IT–150 Hydrostatic Tank Transmitter
0208
IT–160 Micro Remote Control Unit
EEEE
hex
Instruction data type memory size (4 bytes in extended)
FFFF
hex
Variable data type memory size (4 bytes in extended)
GGGG
hex
Constant data type memory size (4 bytes in extended)
IIII
hex
Local input/output memory size (4 bytes in extended)
JJJJ
hex
Global input/output memory size (4 bytes in extended)
KKKK ...
hex
Total memory size (excluding input and output)
TIWAY 1 Ti505 NIM User Manual
NIM Primitives
4-25