Download PowerShield® Platinum
Transcript
PowerShield® Platinum USER Manual To connect mains cables to the respective input terminals: Mains Connection – Three Phase Connect the power supply cables N-R-S-T to the input terminals (X4), (X1), (X2) and (X3), noting the order of neutral and phases Indicated on the label of the UPS and in the manual. If the order of the phases is not correct the UPS will indicate a ‘Phase Rot’ error when activated and will not operate. Mains Connection – Single Phase Connect the power supply cables R-N to the input terminals (X1) and (X4), Noting the order of phase and neutral indicated on the label of the device If the order of the phases is not correct the device will not operate. 4.3.2 Independent Static Bypass Connection To connect the cables of static bypass Supply to the terminals of the UPS Bypass input:. Three Phase System : Connect the power supply cables N-R-S-T to the static bypass line terminals (X17), (X14), (X15) and (X16), in the correct order of neutral and phases indicated on the label of the UPS. If the order of the phases is not correct, a ‘Phase Rot’ message will appear on startup and the device will not operate. 4.3.3 Output Terminal Connections Three phase : Connect the load cables N-U-V-W to the output terminals (X9), (X6), (X7) and (X8), in the correct order of neutral and phases indicated on the label of the device.. Single Phase : Connect the loads cables U-N to the output terminals (X6) and (X9), in the correct order.. With respect to downstream protection that must be placed on the output of the UPS, we recommend that the output power should be distributed in at least four circuits each having a magnetic thermal protection breaker of a value of one quarter of the nominal power. This type of power distribution will mean that in the event of a breakdown in any of the load connected to the UPS causing a short-circuit, it will affect no more than the line that is faulty. Single Phase System: Connect the power supply cables R-N to the static bypass line terminals (X1) and (X4), in the correct order of phase and neutral indicated on the label of the UPS. If the order of the phases is not correct, the device will not operate. Two Supply Sources If mains is supplied to the bypass and the main input of the UPS from two different sources, ie Different transformers or Mains and Generator, then if the respective source neutrals cannot be made common, an isolation transformer must be used in the main and the bypass input of the UPS. 16 www.powershield.com.au ©PowerShield 2012