Download PowerShield® Platinum

Transcript
PowerShield® Platinum USER Manual
To connect mains cables to the respective input terminals:
Mains Connection – Three Phase
Connect the power supply cables N-R-S-T to the input terminals
(X4), (X1), (X2) and (X3), noting the order of neutral and phases
Indicated on the label of the UPS and in the manual. If the order of
the phases is not correct the UPS will indicate a ‘Phase Rot’ error when
activated and will not operate.
Mains Connection – Single Phase
Connect the power supply cables R-N to the input terminals (X1) and (X4),
Noting the order of phase and neutral indicated on the label of the device
If the order of the phases is not correct the device will not operate.
4.3.2
Independent Static Bypass Connection
To connect the cables of static bypass Supply to the terminals of
the UPS Bypass input:.
Three Phase System :
Connect the power supply cables N-R-S-T to the static bypass line
terminals (X17), (X14), (X15) and (X16), in the correct order of neutral
and phases indicated on the label of the UPS. If the order of the phases
is not correct, a ‘Phase Rot’ message will appear on startup and the device
will not operate.
4.3.3
Output Terminal Connections
Three phase :
Connect the load cables N-U-V-W to the output
terminals (X9), (X6), (X7) and (X8), in the correct order
of neutral and phases indicated on the label of the
device..
Single Phase :
Connect the loads cables U-N to the output terminals
(X6) and (X9), in the correct order..
With respect to downstream protection that must be
placed on the output of the UPS, we recommend that
the output power should be distributed in at least four
circuits each having a magnetic thermal protection
breaker of a value of one quarter of the nominal
power. This type of power distribution will mean that in
the event of a breakdown in any of the load connected
to the UPS causing a short-circuit, it will affect no more
than the line that is faulty.
Single Phase System:
Connect the power supply cables R-N to the static bypass line
terminals (X1) and (X4), in the correct order of phase and neutral
indicated on the label of the UPS.
If the order of the phases is not correct, the device will not
operate.
Two Supply Sources
If mains is supplied to the bypass and the main input of the UPS from
two different sources, ie Different transformers or Mains and Generator,
then if the respective source neutrals cannot be made common, an isolation
transformer must be used in the main and the bypass input of the UPS.
16
www.powershield.com.au
©PowerShield 2012