Transcript
WIN-9_F Series User Manual · Terminal S3 function: set to P036 · Terminal S4 function: set to P037 · Terminal S5 function: set to P038 · Terminal S6 function: set to P039 Setting Name Description 0 REV run command (2-wire sequence) 1 FWD/REV run command(3-wire sequence) Only parameter P035 can be set to this value. 2 External fault (NO contact input) 3 External fault (NC contact input) Inverter stops at fault when external fault signal is input. Digital operator displays “EF0”. 4 Fault reset Resets fault. Fault reset is disabled during run command input. 5 LOCAL/REMOTE selection - 6 Serial communication/control circuit terminal selection - 7 Fast stop Decelerates to stop by decel time 2 (P022) when fast stop is input. 8 Master frequency reference inputselection level selection Master frequency reference input level (voltage input at“open”current input at“closed”) can be selected. 9 Multi-step speed reference 1 10 Multi-step speed reference 2 11 Jog frequency selection 12 Accel/decel time selection 13 External baseblock (NO contact input) 14 External baseblock (NC contact input) Coasting signal. Motor starts coasting when the signal Digital operator displays “bb” (blinking). 15 Search command from maximum frequency Speed search command signals. 16 Search command from set frequency 17 Constant setting enable/disable 18 PID integral value reset 19 PID control disable 20 Timer function - 21 OH3 (inverter overheat alarm) When this signal is input, the digital opertor displays “OH3” (blinking). Inverter continues operation. 22 Analog reference sample/hold Analog frequency reference is sampled at closed and held at open. 25 UP/DOWN command Only parameter P039 can be set to this value. 26 Loop test Only parameter P039 can be set to this value. - Permission or prohibition of constant setting from the digital operator or serial communication (setting disabled at“closed”, enabled at“open”) can be selected. - ● 62 ●