Overview of Alarms
01/2008
NCK alarms
17120
Channel %1 block %2 analog input no. %3 not activated
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Input number
Definitions:
An attempt has been made by means of the system variable $A_INA[n] to read an analog input n that
has not been activated by the MD 10300 FASTIO_ANA_NUM_INPUTS.
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Please inform the authorized personnel/service department. Modify part program or machine data
accordingly.
Program Continuation:
Clear alarm with NC START or RESET key and continue the program.
17130
Channel %1 block %2 analog output no. %3 not activated
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = No. of output
Definitions:
An attempt has been made by means of the system variable $A_OUTA[n] to write or read an analog
output n that has not been activated by the MD 10310 FASTIO_ANA_NUM_OUTPUTS.
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Please inform the authorized personnel/service department. Modify part program or machine data
accordingly.
Program Continuation:
Clear alarm with NC START or RESET key and continue the program.
17140
Channel %1 block %2 NCK output %3 is assigned to a function via
machine data
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = No. of output
Definitions:
The programmed digital/analog output is assigned to an NC function (e.g. software cams).
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Please inform the authorized personnel/service department. Use another output or deactivate concurrent NC function via MD.
Program Continuation:
Clear alarm with NC START or RESET key and continue the program.
17150
Channel %1 block %2 maximum of %3 NCK outputs programmable in the
block
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Quantity
Definitions:
No more than the specified number of outputs may be programmed in an NC block.
The quantity of hardware outputs is defined in the MDs:
10360 FASTIO_DIG_NUM_OUTPUTS and
10310 FASTIO_ANA_NUM_OUTPUTS
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Program fewer digital/analog outputs in a block. The specified maximum number applies in each case
separately for analog or digital outputs. If necessary, program two NC blocks.
Program Continuation:
Clear alarm with NC START or RESET key and continue the program.
2-284
© Siemens AG, 2008. All Rights Reserved
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 01/2008