Chapter 5
Basic Operation
Parameter F1-04 sets the stopping method that is used when a PG speed deviation fault occurs.
Parameter
number
F1-04
Display name
Setting
range
PG Deviation Sel
0 to 3
Units
---
Default
setting
3
Valid access levels*
V/f
V/f with Open Loop Flux
Control
PG
Vector
Vector
--B
--B
Note B: Basic or Advanced
---: Not applicable.
Settings
Setting
0
1
2
3
Name
Ramp to Stop
Coast to Stop
Fast Stop
Alarm Only
Function
Deceleration stop using deceleration time 1 (C1-02).
Free-run stop
Emergency stop using the fast-stop time (C1-09).
Continue operation (Display “DEV” and continue control.)
Parameter F1-10 sets the PG speed deviation detection level as a percentage of the maximum output
frequency. Parameter F1-11 sets the length of time that the difference between the motor speed and
reference speed must exceed the PG speed deviation detection level in order to generate a PG speed
deviation fault (DEV).
Parameter
number
F1-10
F1-11
Display name
Setting
range
PG Deviate Level
PG Deviate Time
0 to 50
0.0 to 10.0
Units
%
s
Default
setting
10
0.5
Valid access levels*
V/f
V/f with Open Loop Flux
Control
PG
Vector
Vector
--A
--A
--A
--A
Note A: Advanced
---: Not applicable.
5-5-4 Speed Loop (ASR) Structure
The following block diagram shows the structure of the speed loop.
Frequency
reference
Detected
speed
Output frequency
Change
limiter
Limiter
Gain Settings
When using “V/f control with PG feedback,” set the gain at the minimum frequency and maximum frequency.
5-48