Chapter 5 Basic Operation Parameter F1-04 sets the stopping method that is used when a PG speed deviation fault occurs. Parameter number F1-04 Display name Setting range PG Deviation Sel 0 to 3 Units --- Default setting 3 Valid access levels* V/f V/f with Open Loop Flux Control PG Vector Vector --B --B Note B: Basic or Advanced ---: Not applicable. Settings Setting 0 1 2 3 Name Ramp to Stop Coast to Stop Fast Stop Alarm Only Function Deceleration stop using deceleration time 1 (C1-02). Free-run stop Emergency stop using the fast-stop time (C1-09). Continue operation (Display “DEV” and continue control.) Parameter F1-10 sets the PG speed deviation detection level as a percentage of the maximum output frequency. Parameter F1-11 sets the length of time that the difference between the motor speed and reference speed must exceed the PG speed deviation detection level in order to generate a PG speed deviation fault (DEV). Parameter number F1-10 F1-11 Display name Setting range PG Deviate Level PG Deviate Time 0 to 50 0.0 to 10.0 Units % s Default setting 10 0.5 Valid access levels* V/f V/f with Open Loop Flux Control PG Vector Vector --A --A --A --A Note A: Advanced ---: Not applicable. 5-5-4 Speed Loop (ASR) Structure The following block diagram shows the structure of the speed loop. Frequency reference Detected speed Output frequency Change limiter Limiter Gain Settings When using “V/f control with PG feedback,” set the gain at the minimum frequency and maximum frequency. 5-48
Related documents
3G3FV User`s Manual
SYSDRIVE 3G3HV
3G3FV User`s Manual - Products
CX-Drive Operation Manual
Chapter 5 Basic Operation
"user manual"
USER`S MANUAL SYSDRIVE 3G3MV Multi-function
Motion & Drives - Frequency Inverters
3E3EV Multi-function User`s Manual
Chapter 10
Siemens SITRANS FC410 Coriolis Mass Flowmeter with Modbus
USER`S MANUAL DeviceNet (CompoBus/D