Download Chapter 6 Advanced Operation
Transcript
Chapter 7 Parameter Lists Sequence for Reference: d4 Para meter No. d4-01 Name Setting range Default setting Reference frequency hold function selection Sets whether or not frequencies on hold will be recorded. 0: Disabled (when operation is stopped or the power is turned on again starts at 0.) 1: Enabled (when operation is stopped or the power is turned on again starts at the previous hold frequency.) Note: This function is available when the multi-function inputs “accel/decel Ramp Hold” or “UP/DOWN” commands (MOP increase/decrease) are set. 0, 1 Trim control level Sets the increase/decrease frequency for analog frequency references as a percentage of the maximum frequency. Note: This function is available when the multi-function inputs “Trim Ctl Increase” or “Trim Ctl Decrease” is set. Trim Control Lvl Control mode 0 Changes during operation NO A 0 to 100 25 NO A Setting range Default setting 0: Speed control (C5-01 to C5-07) 1: Torque control Note: This function is only available in flux vector control mode. To use the function for switching between speed and torque control, set to 0 and set the multi-function input to “speed/torque control change.” 0, 1 0 Changes during operation NO X Sets the torque reference delay time in ms units. Note: This function can be used to adjust the noise of the torque control signal or the responsiveness with the host controller. When vibration occurs during torque control, increase the set value. 0 to 1000 0 NO X Display name MOP Ref Memory d4-02 Description V/f control V/f with PG Page Open loop vector Flux vector A A A 6-65 A A A 6-66 Torque Control: d5 Para meter No. d5-01 Name Torque control selection Torq Control Sel d5-02 Description Display name Torque reference delay time Torq Ref Filter Control mode V/f control V/f with PG Page Open loop vector Flux vector X X A 6-20, 6-27 X X A 6-25 7-23