December 2008
12" Display Models
Table 4-4: Enclosure Selection — 12" Display Models
Enclosure Size
Average Internal Temperature Rise
at Rated Heat Output
20 x 20 x 6
10.5°C
20 x 24 x 6
9.5°C
20 x 20 x 8
9.5°C
20 x 24 x 8
8°C
15" Display Models
Table 4-5: Enclosure Selection — 15" Display Models
Enclosure Size
Average Internal Temperature Rise
at Rated Heat Output
20 x 24 x 6
12.5°C
20 x 20 x 8
12°C
20 x 24 x 8
10°C
24 x 24 x 8
9.5°C
Blind Node Models
Table 4-6: Enclosure Selection — Blind Node Models
Enclosure Size
Average Internal Temperature Rise
at Rated Heat Output
16 x 20 x 4
9.5°C
16 x 20 x 6
9°C
20 x 20 x 6
6.5°C
20 x 24 x 6
6°C
Notes:
●
These tables are based on the following assumptions:
– No additional peripherals are installed
– Enclosure is fabricated from cold rolled steel
– All sides of the enclosure are non-insulated (free standing)
– Recommended minimum clearance between the PanelMate ePro PS unit and the top
and bottom of the enclosure
– No other heat-generating equipment is installed in the enclosure
– Maximum CPU usage
●
The temperature rise shown represents the temperature rise in the enclosure above the
outside temperature. For example: if the temperature outside the enclosure is 35°C and
the temperature rise in the enclosure is 10°C, then the average temperature inside the
enclosure will be 45°C. Keep in mind that there will be areas warmer than the average
inside the enclosure.