Wire Size Tables 230 VAC 3 Phase 60 Hz Input HP 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 Full Load AC Amps 17 25 32 49 63 79 93 124 156 184 229 300 380 450 460 VAC 3 Phase 60 Hz Input Minimum Wire Size Circuit Breaker for 40 ft length AC Amps at 250VAC 12 AWG 25 10 AWG 30 8 AWG 40 6 AWG 70 4 AWG 90 3 AWG 100 1 AWG 125 00 AWG 175 000 AWG 200 0000 AWG 225 300 MCM 300 500 MCM 400 (2) 250 MCM 500 (2) 350 MCM 600 HP 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 Full Load AC Amps 8.6 11 13.5 21 27 34 40 54 67 80 99 133 167 202 266 375 240 VDC Armature HP 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 Full Load DC Amps 19 28 36 54 70 87 105 139 173 205 254 337 325 504 Minimum Wire Size for 40 ft length 10 AWG 8 AWG 6 AWG 4 AWG 2 AWG 1 AWG 0 AWG 0000 AWG 250 MCM 300 MCM 500 MCM (2) 250 MCM (2) 350 MCM (2) 500 MCM Minimum Wire Size Circuit Breaker for 40 ft length AC Amps at 600VAC 14 AWG 10 14 AWG 15 12 AWG 20 10 AWG 30 8 AWG 35 8 AWG 40 6 AWG 50 4 AWG 70 4 AWG 90 3 AWG 100 1 AWG 125 00 AWG 175 0000 AWG 225 250 MCM 300 (2) 000 AWG 400 (2) 250 MCM 500 500 VDC Armature DC Fuse Amps (if used) 25 40 50 70 100 150 150 200 250 300 400 600 600 800 HP 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 150 VDC Field Wire Size for 40 ft Length 5 - 75 H.P. : 14 AWG 100 - 200 H.P. : 12 AWG Full Load DC Amps 10 12 15 23 30 38 45 60 75 90 110 148 185 218 295 408 Minimum Wire Size for 40 ft length 12 AWG 12 AWG 10 AWG 8 AWG 8 AWG 6 AWG 4 AWG 3 AWG 2 AWG 1 AWG 00 AWG 0000 AWG 300 MCM (2) 000 AWG (2) 250 MCM (2) 350 MCM DC Fuse Amps (if used) 15 20 25 35 45 60 70 100 150 150 200 250 300 400 600 600 300 VDC Field Wire Size for 40 ft Length 5 - 75 H.P. : 14 AWG 100 - 200 H.P. : 14 AWG Elementary Power Connection Diagram DC Motor A- DC Drive A A+ L1F L2F L1C L2C L1S L2S L3S ABC FIELD 3A fuse 115V Page 6 F+ L1 L2 L3 L1 L2 L3 F- L1C and L2C are alternately marked 115V.