Download EXPERT PN110
Transcript
EXPERT PN110 5.4.1.3 Resetting the Actuator’s Position Resetting the actuator’s position is used to clear accumulated time offets caused by the frequent openings and closings of the inlet. The controller resets the actuator’s position at regular intervals to make sure the inlet position is always accurate. This reset is performed automatically according to one of these two methods: • • Reset the minimum position only (Close mode) Each time a reset is performed, the inlet totally closes. Once the actuator’s position is reset, the inlet returns to its previous position. The “Close” pilot light of the inlet flashes while the controller closes the inlet. Reset toward the nearest position (Open/Close mode) If the current inlet position is higher than 50% at the reset time, the controller fully opens the inlet to reset the actuator’s position; if the current inlet position is lower than 50%, the controller closes the inlet to perform the reset. This way, the inlet never closes when the room temperature already asks for a wide opening. The “Open” or “Close” pilot light of the inlet flashes while the controller moves the inlet. Make sure limit switches are located at both ends of the actuators when using this resetting method. • Select the INLET menu with the menu select buttons. • Select "1. Stage Opening" with the menu select buttons. Accessible if the inlet is enabled (section 5.16.3). • Use the arrow keys to select the parameters that are presented below. To adjust the value of a parameter, press Edit then use the arrow key to modify the parameter's value. Press Edit again to validate the new value. 4. Inlet Reset Inlet Auto Reset Reset Mode Op/Cl Reset Now? No Day Time 06:00 am Period 3 Delay 02:00 Inlet reset mode: Select the desired reset mode: “Op/Cl” to reset the actuator toward its nearest position; select “Close” to reset the actuator toward its closed position only or select “Off” to disable the automatic reset. Inlet reset now? Select “Yes” to reset the actuator’s position now. Day time: Set the time at which resets are performed. Period: Enter the frequency of inlet resets. A reset can be performed once every 1-7 days. Reset delay: During a reset, the controller opens or closes the inlet during this delay, or up until a limit switch is reached. The reset delay should be set to the same time value or higher than the total opening time (as defined in the previous section). EXPERT PN110 rev.12 19