5.4.1.3 Resetting the Actuator’s Position
Resetting the actuator’s position is used to clear
accumulated time offets caused by the frequent
openings and closings of the inlet. The controller
resets the actuator’s position at regular intervals
to make sure the inlet position is always accurate.
This reset is performed automatically according to
one of these two methods:
•
•
Reset the minimum position only
(Close mode)
Each time a reset is performed, the inlet totally closes. Once the actuator’s position is
reset, the inlet returns to its previous position. The “Close” pilot light of the inlet
flashes while the controller closes the inlet.
Reset toward the nearest position
(Open/Close mode)
If the current inlet position is higher than
50% at the reset time, the controller fully
opens the inlet to reset the actuator’s position; if the current inlet position is lower than
50%, the controller closes the inlet to perform the reset. This way, the inlet never closes
when the room temperature already asks for
a wide opening. The “Open” or “Close” pilot
light of the inlet flashes while the controller
moves the inlet.
Make sure limit switches are
located at both ends of the
actuators when using this resetting method.
•
Select the INLET menu with the menu select
buttons.
•
Select "1. Stage Opening" with the menu select buttons.
Accessible if the inlet is enabled (section 5.16.3).
•
Use the arrow keys to select the parameters
that are presented below. To adjust the value
of a parameter, press Edit then use the arrow
key to modify the parameter's value. Press Edit
again to validate the new value.
4. Inlet Reset
Inlet Auto Reset
Reset Mode
Op/Cl
Reset Now?
No
Day Time 06:00 am
Period
3
Delay
02:00
Inlet reset mode:
Select the desired reset mode: “Op/Cl” to reset the actuator toward its nearest position;
select “Close” to reset the actuator toward its
closed position only or select “Off” to disable
the automatic reset.
Inlet reset now? Select “Yes” to reset the
actuator’s position now.
Day time:
Set the time at which resets are performed.
Period:
Enter the frequency of inlet resets. A reset can
be performed once every 1-7 days.
Reset delay:
During a reset, the controller opens or closes
the inlet during this delay, or up until a limit
switch is reached. The reset delay should be
set to the same time value or higher than the
total opening time (as defined in the previous
section).