Download - Columbia Machine

Transcript
English-6
PowerFlex 70 Adjustable Frequency AC Drive Quick Start
Step 3
Wire the Drive – Wire Recommendations
Type
Power
Wire Type(s)
Description
• Four tinned copper
Standard 600V, 90°C (194°F)
conductors with XLPE
(1)
XHHW2/RHW-2
insulation.
Anixter
B209500-B209507, Belden • Copper braid/aluminum foil
combination shield and
29501-29507, or
tinned copper drain wire.
equivalent
• PVC jacket.
Signal
Standard Belden 8760/9460(or
0.750 mm2 (18AWG), twisted
(1) (2) (3)
Analog I/O equiv.)
pair, 100% shield with drain.
Belden 8770(or equiv.)
0.750 mm2 (18AWG), 3
cond., shielded for remote pot
only.
Digital I/O Shielded Multi-conductor shielded 0.750 mm2 (18AWG), 3
(1) (2) (3)
cable such as Belden
conductor, shielded.
8770(or equiv.)
(1)
(2)
(3)
Min. Insulation
Rating
300V,
75-90 degrees
C (167-194
degrees F)
300V,
60 degrees C
(140 degrees F)
Control and signal wires should be separated from power wires by at least 0.3 meters (1 foot).
If the wires are short and contained within a cabinet which has no sensitive circuits, the use of
shielded wire may not be necessary, but is always recommended.
I/O terminals labeled “(–)” or “Common” are not referenced to earth ground and are designed to
greatly reduce common mode interference. Grounding these terminals can cause signal noise.
Terminal Block Specifications
Name
Frame Description
Power Terminal A, B & Input power and
Block
C
motor connections
D
Input power and
motor connections
E
Input power and
motor connections
Wire Size Range (1)
Maximum Minimum
3.5 mm2 0.3 mm2
(12 AWG) (22 AWG)
8.4 mm2 0.8 mm2
(8 AWG) (18 AWG)
25.0 mm2 2.5 mm2
(3 AWG) (14 AWG)
I/O Terminal
Block
1.5 mm2 0.05 mm2 0.55 N-m 0.5 N-m
(16 AWG) (30 AWG) (4.9 lb.-in.) (4.4 lb.-in.)
All
Signal & control
connections
SHLD Terminal All
(1)
Terminating point
for wiring shields
—
—
Torque
Maximum
0.66 N-m
(5.5 lb.-in.)
1.7 N-m
(15 lb.-in.)
2.71 N-m
(24 lb.-in.)
Recommended
0.6 N-m
(5 lb.-in.)
1.4 N-m
(12 lb.-in.)
2.71 N-m
(24 lb.-in.)
1.6 N-m
1.6 N-m
(14 lb.-in.) (14 lb.-in.)
Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
Power & Ground Wiring
L1
R
L2
S
L3
T
Required
Input Fusing
Required Branch
Circuit Disconnect
PE
PE
T1
U
T2
V
T3
W
+DC BRK