Download - Columbia Machine
Transcript
English-6 PowerFlex 70 Adjustable Frequency AC Drive Quick Start Step 3 Wire the Drive – Wire Recommendations Type Power Wire Type(s) Description • Four tinned copper Standard 600V, 90°C (194°F) conductors with XLPE (1) XHHW2/RHW-2 insulation. Anixter B209500-B209507, Belden • Copper braid/aluminum foil combination shield and 29501-29507, or tinned copper drain wire. equivalent • PVC jacket. Signal Standard Belden 8760/9460(or 0.750 mm2 (18AWG), twisted (1) (2) (3) Analog I/O equiv.) pair, 100% shield with drain. Belden 8770(or equiv.) 0.750 mm2 (18AWG), 3 cond., shielded for remote pot only. Digital I/O Shielded Multi-conductor shielded 0.750 mm2 (18AWG), 3 (1) (2) (3) cable such as Belden conductor, shielded. 8770(or equiv.) (1) (2) (3) Min. Insulation Rating 300V, 75-90 degrees C (167-194 degrees F) 300V, 60 degrees C (140 degrees F) Control and signal wires should be separated from power wires by at least 0.3 meters (1 foot). If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary, but is always recommended. I/O terminals labeled “(–)” or “Common” are not referenced to earth ground and are designed to greatly reduce common mode interference. Grounding these terminals can cause signal noise. Terminal Block Specifications Name Frame Description Power Terminal A, B & Input power and Block C motor connections D Input power and motor connections E Input power and motor connections Wire Size Range (1) Maximum Minimum 3.5 mm2 0.3 mm2 (12 AWG) (22 AWG) 8.4 mm2 0.8 mm2 (8 AWG) (18 AWG) 25.0 mm2 2.5 mm2 (3 AWG) (14 AWG) I/O Terminal Block 1.5 mm2 0.05 mm2 0.55 N-m 0.5 N-m (16 AWG) (30 AWG) (4.9 lb.-in.) (4.4 lb.-in.) All Signal & control connections SHLD Terminal All (1) Terminating point for wiring shields — — Torque Maximum 0.66 N-m (5.5 lb.-in.) 1.7 N-m (15 lb.-in.) 2.71 N-m (24 lb.-in.) Recommended 0.6 N-m (5 lb.-in.) 1.4 N-m (12 lb.-in.) 2.71 N-m (24 lb.-in.) 1.6 N-m 1.6 N-m (14 lb.-in.) (14 lb.-in.) Maximum/minimum sizes that the terminal block will accept - these are not recommendations. Power & Ground Wiring L1 R L2 S L3 T Required Input Fusing Required Branch Circuit Disconnect PE PE T1 U T2 V T3 W +DC BRK