Installation and Wiring Wiring 2-13 Power, Control, and Ground Wiring Table 2.1 provides the power, control, safety inputs, and ground wire capacities, and the tightening torque requirements. The power, control, ground, and safety monitor terminals will accept a maximum of two wires per terminal. Table 2.1 Power, Control, Safety Input, Ground Wire Size, and Torque Specifications Terminals Wire Size Torque Wire Strip Length Power and Ground Primary/Secondary Terminal: 1.5…4.0 mm2 (#16 …#10 AWG) Primary Terminal: 10.8 lb.-in. (1.2 N•m) Secondary Terminal: 4.5 lb.-in (0.5 N•m) 0.35 in. (9 mm) Control and Safety Inputs 1.0 mm2…4.0 mm2 (#18…#10 AWG) 6.2 lb.-in (0.7 N•m) 0.35 in. (9 mm)