Download L-INX User Manual
Transcript
L-INX/L-GATE User Manual 276 LOYTEC 3. Click on the Create with DP button. This opens the Import Modbus Device Template dialog shown in Figure 212. 4. Press the 5. After selecting the file, the device information is displayed. 6. Press Import for importing the template or Cancel for closing the dialog without any changes. 7. When a template is imported, a folder with the name of the device is created. Under this folder a Datapoints folder containing the data points from the template file is created. 8. The created device is shown in the list together with the number of data points. button and select a template file from the Open dialog. To Remove a Modbus Device 1. Select the device which has to be removed, also multi-select is possible. 2. Press the Remove Device button. If the device already has data points, these data points have to be deleted before the remove can be performed. To Change the Properties of a Modbus Device 1. Select the device. This shows the device properties. 2. Update the properties which have to be changed. 3. Press the button Update Device. 4. When the device type is changed, it is verified that no device with the address exists on the appropriate port – on RS485 the device address has to be unique, on TCP the device IP address has to be unique. 11.5.2 Manual Configuration of Data Points It is possible to manually configure Modbus data points. Manual configuration is done by specifying all information, the Modbus device manufacturer provides. To Manually Create an Modbus Data Point Version 4.4 1. Click on the Modbus port Datapoints folder. 2. Right-click in the data point list view and select New Datapoint… in the context menu. LOYTEC electronics GmbH