Download EV1000 Series General Purpose Variable Speed Drive User Manual

Transcript
Appendix 1
Parameter Set
127
Group 9: Enhanced Function
Para.
Name
Range
0.000~65.535 ( km)
F9.15 Actual length
Unit
(save after power off)
Default Modification
0.001
0.000
( km)
( km)
○
F9.16 Length factor
0.001~30.000
0.001
1.000
○
F9.17 Length calibration
0.001~1.000
0.001
1.000
○
F9.18 Shaft circumference
0.01~100.00 ( cm)
0.01
10.00
( cm)
( cm)
1
1
○
1
0
×
○
1~9999
F9.19 Pulse per revolution
F9.20
Low voltage
0: disabled
compensation
1: enabled (low voltage compensation)
Freq. decrease rate
F9.21 during voltage
0.00~99.99Hz/s
0.01Hz/s 10.00Hz/s
○
compensation
Conditions of restart after 0: disabled
F9.22
F9.23
power failure
Restart delay after power
failure
1
0
×
0.1s
0.5s
○
1: enabled
0.0~10.0s
Note:
Actual length (km) =counting value×F9.18÷F9.19×F9.16 ÷F9.17 ÷100÷1000。
Group FA: Reserved
Para.
FA.00~FA.11
Name
Reserved
Range
-
Unit
-
Default
0
EV1000 Series General Purpose Variable Speed Drive
Modification
*