Download User manual
Transcript
ENG The generic alarm functions can be associated with an alarm already featured on UltraCella (for example CHt, high condenser temperature alarm, or LP, low pressure alarm), or to digital inputs D12/DI3, which therefore need to be configured specifically. Par. H1 H5 Par. A5 A9 Description Configuration of digital input DI2 15 = alarm from generic function Configuration of digital input DI3 15 = alarm from generic function Def 0 Min 0 Max 15 U.o.M - 0 0 15 - Description Def AUX1 output configuration 0 8 = Generic ON/OFF control function 1 9 = Generic ON/OFF control function 2 AUX2 output configuration 0 8 = Generic ON/OFF control function 1 9 = Generic ON/OFF control function 2 Min 0 Max 17 U.o.M - 0 17 - 6.18.1 ON/OFF control UltraCella can manage 2 ON/OFF control functions, with direct or reverse action and settable control set point and differential. The control variable is defined by parameter AS1 (AS2). Par. AS1 r1S SS1 Description Def ON/OFF control 1: control variable 3 configuration 0 Sm 8 generic temperature probe 2 1 Sd1 9 generic temperature probe 3 2 Sr 10 generic temperature probe 4 3 Sv 11 generic temperature probe 5 4 Sd2 12 generic humidity probe 4 5 Sc 13 generic humidity probe 5 6 SA 14 generic pressure probe 5 7 Su ON/OFF control 1: mode 0 0/1=direct/reverse ON/OFF control 1: set point 0,0 rS1 ON/OFF control 1: differential AS2 SS2 ON/OFF control 2: control variable configuration 0 Sm 8 generic temperature probe 2 1 Sd1 9 generic temperature probe 3 2 Sr 10 generic temperature probe 4 3 Sv 11 generic temperature probe 5 4 Sd2 12 generic humidity probe 4 5 Sc 13 generic humidity probe 5 6 SA 14 generic pressure probe 5 7 Su ON/OFF control 2: mode 0/1=direct/reverse ON/OFF control 2: set point 0,0 rS2 ON/OFF control 2: differential 2,0 r2S 2,0 3 Min 0 Max U.o.M. 14 - Fig. 6.ah For each ON/OFF control function, two alarm absolute thresholds and an alarm notification delay can be set. 0 1 - -50,0 200,0 °C/°F/ 0,0 100,0 rH%/ -20,0 999 bar/ psi 0,1 20,0 °C/°F/ rH%/ bar/ psi 0 14 - Description Def ON/OFF control 1: absolute low 0,0 alarm threshold AH1 ON/OFF control 1: absolute high alarm threshold 0 Ad1 AL2 ON/OFF control 1: alarm delay ON/OFF control 2: absolute low alarm threshold 0 0,0 AH2 ON/OFF control 2: absolute high alarm threshold 0 Ad2 ON/OFF control 2: alarm delay 0 Min -50.0 0.0 -20.0 -50.0 0.0 -20.0 0 -50.0 0.0 -20.0 -50.0 0.0 -20.0 0 Max 200.0 100.0 999 200.0 100.0 999 250 200.0 100.0 999 200.0 100.0 999 250 U.o.M °C/°F/ rH%/ bar/psi °C/°F/ rH%/ bar/psi min °C/°F/ rH%/ bar/psi °C/°F/ rH%/ bar/psi min The following alarms are generated by the functions: • GL1,GL2: alarms when exceeding low thresholds AL1, AL2 • GH1, GH2: alarms when exceeding high thresholds AH1, AH2 0 0 1 Example 1: ON/OFF control 1 based on pressure (input B5, 4 to 20 mA) with direct action via AUX1. Control set point 15 bars, differential 3 bars. Set: • /P5 = 0 -> input B5 to 4 to 20 mA • /A5 = 4 -> generic pressure probe 5 • AS1 = 14 -> generic pressure probe 5 • r1S = 0 -> direct action • SS1 = 15 -> control set point 15 bars • rS1 = 3 -> differential 3 bars • H1 = 8 -> output AUX1 for ON/OFF control 1 - -50,0 200,0 °C/°F/ 0,0 100,0 rH%/ -20,0 999 bar/ psi 0,1 20,0 °C/°F/ rH%/ bar/ psi Example 2: ON/OFF control 2 based on humidity (input B4, 0 to 10 V) with reverse action on AUX2. Control set point 75% rH, differential 10% rH. Set: • /P4 = 2 -> input B4 to 0 to 10 V • /A4 = 4 -> generic humidity probe 4 • AS2 = 12 -> generic humidity probe 4 • r2S = 1 -> reverse action • SS2 = 75 -> control set point 75% rH • rS2 = 10 -> differential 10% rH • H5 = 9 -> output AUX2 for ON/OFF control 2 To enable the function, set AS1/AS2 to a value greater than 0. To use outputs AUX1/AUX2 for generic ON/OFF functions, set parameters H1/ H5. UltraCella +0300083EN - rel. 1.6 - 31.10.2015 Par. AL1 58