Download Catalogue
Transcript
7 PROGRAMMING MODE Function : To set time delay COMP. TIME DELAY between comp. relay restart 0Min 30MIn 3Min 9B PROGRAMMING MODE Function : If P8=1 Cyclic OFF CYC. OFF TIME time . P6 Parameter time. OFF Time Parameter To change the P6 parameter, press the SET key. Use UP/DOWN key to set desired value. To change the Use UP/DOWN key to set Off time parameter, desired value. press the SET key. This parameter is used to protect the compressor from restarting in a short period of time. It can be set between 0 to 30Min. PROGRAMMING MODE Function : To set drip time for DRIP TIME defrost water to drain out. 10 To change the P9 parameter, press the SET key. To change the P8 parameter, press the SET key. 11 0Min 20MIn 1Min 12 0 2 To change the L2 parameter, press the SET key. 1 13 50OC 2OC 0Min 99Min 1Min 0 1 1 Use UP/DOWN key to set desired value. PROGRAMMING MODE Function : Evap. Fan FAN IF COMP OFF operation when compressor is L3 Parameter 2Min 60Min 10Min To change the L3 parameter, press the SET key. off. Use UP/DOWN key to set desired value. 0 = Evap. fan OFF when compressor is OFF. Use UP/DOWN key to set desired value. 1 = Evap. fan will be stay ON when compressor will be off. This is cyclic ON time of Comp relay. Example : If this parameter is set to 1, then when comp. OFF, evap. fan will remain ON. This parameter will be active only when P8 = 1. 07 -50OC Example : If this is set 3 minutes, the evap. fan relay will cutoff at the temp. set by L1 parameter(Fan stop temp.) but the fan will not come on for a minimum of 3 minutes if L4 is achieved earlier. ON Time Parameter To change the On time parameter, press the SET key. 10Min Use UP/DOWN key to set desired value. This setting is used to limit maximum temperature beyond which the evap. fan will cutoff PROGRAMMING MODE Function : To set time delay FAN TIME DELAY between evap. fan relay L2 Parameter restart time. Use UP/DOWN key to set desired value. PROGRAMMING MODE Function : If P8=1 Cyclic ON CYC. ON TIME time . 30MIn Use UP/DOWN key to set desired value. PROGRAMMING MODE Function : Evap. Fan stop coil FAN STOP TEMP. temp. L1 parameter To change the L1 parameter, press the SET key. 0 = Compressor relay ON. 1 = Compressor relay performs a duty cycle of 'on' minutes and 'oF' minutes(see next two parameter). (see Sr. 9A and 9B) 2 = Compressor relay OFF. 9A 0Min Example : If P9 = 10 minutes, alarm for door open fault will be generated if door open fault present for 10 minutes. Use UP/DOWN key to set desired value. PROGRAMMING MODE Function : To set comp. Relay COMP IN PRB FAIL status on room probe failure. P8 Parameter PROGRAMMING MODE Function : To set door open DOOR ALARM DLY alarm delay. P9 Parameter This is time for which the Fan, Compressor, Condenser, Heater will stay OFF so that the defrost water can drip and drain out. It can be set between 0 to 20Min. 9 4Min This parameter will be active only when P8 = 1. P7 Parameter To change the P7 parameter, press the SET key. 20Min This is cyclic OFF time of Comp relay. Example : If this parameter set at 3 minutes, the relay will cutoff at set temperature, but will not restart for a minimum of 3 minutes, even if the differential is achieved earlier. This parameter is good to protect the life of the compressor or even in applications where the probe is placed at places where there are sudden and short changes in temperature like above a cold room door. 8 3Min CRC1100A CRC1100A 08