5.6.2.a Ramp 2 (user-optional ramp) This ramp is selected by closing the input for Ramp 2, TB1 – terminals 5 & 6 (see section 4.2.5). If this input is left open, the VMX Series will respond only to Ramp 1 settings as listed above. Since ramp 2 is always used as an alternate to the default Ramp 1, different combinations of ramp profiles can be selected in F010. Refer to Appendix 1 for additional information on ramp profiles. F015 = Initial Torque (Voltage) of Ramp 2 Factory Setting = 60% Range = 0 - 100% Sets the initial voltage of Ramp 2 when F010 = 1 or 4. The initial torque level should be set to provide just enough torque to make the motor shaft begin to rotate while preventing torque shock damage to mechanical components. F016 = Initial Torque (Current) of Ramp 2 Factory Setting = 200% Range = 0 - 600% Sets the initial current of Ramp 2 when F010 = 2 or 3. The initial torque level should be set to provide just enough torque to make the motor shaft begin to rotate while preventing torque shock damage to mechanical components. F017 = Accel Ramp Time of Ramp 2 Factory Setting = 10 seconds Range = 1 - 120 seconds Sets the time between the initial torque set with F015 or F016 and either the Max Current Limit set with F018 or full output voltage. Set the time to enable soft starts without stalls. Also consider the motor’s application. For example, centrifugal pumps may require a shorter time. See notes for F013 for more details. F018 = Max Current Limit of Ramp 2 Factory Setting = 350% Range = 200 - 600% Sets the maximum motor current that the VMX Series starter will allow during ramp 2. (This limit applies to both voltage and current-type ramping.) The current will be limited to this setting until either the motor reaches full speed or the over load protection feature trips (F003). Note: Ramp 2 is often useful as a “bump start” or as a temporary Acrossthe-Line start mode. Consult Appendix 1 for details. VMX Series Digital Solid State Soft Starter User Manual 40 | P a g e