Troubleshooting by Indication on the Remote Controller Remote Controller Display U0 Applicable Models VRVII and II-S Series Method of Error Detection Shortage of refrigerant is detected by discharge pipe thermistor. Error Decision Conditions Micro-computer judge and detect if the system is refrigerant shortage. ∗ Error is not decided while the unit operation is continued. Supposed Causes Shortage of gas or refrigerant system clogging (incorrect piping) Defective pressure sensor Defective outdoor unit PCB Defective thermistor 256 : http://splitoff.ru/tehn-doc.html