Use the GuardPLC Controller as a Scanner Chapter 20 For more information on configuring Logix controllers, refer to Logix5000 Controllers Quick Start, publication 1756-QS001. Configure Connections from the GuardPLC Controller to the Logix Controller 1. In RSNetWorx for EtherNet/IP software, right-click the GuardPLC scanner controller in the graphic view and choose Scanlist Configuration. 2. Right-click the target Logix controller in the Scanlist Configuration dialog box and choose Insert Connection. 3. In this example, the Connection Name is Receive Data From. 4. Enter the name of the producing tag in the Communication Parameters Value field. 5. Make sure that the Input Size value matches the size of the producing tag. 6. Once you have set these properties, click the OK button to apply the changes. RSNetWorx for EtherNet/IP software displays these changes in blue under the I/O module entry. 7. Click Save in RSNetWorx for EtherNet/IP software to download the configuration to the GuardPLC controller. Publication 1753-UM001C-EN-P - March 2010 261