Download GuardPLC Controller Systems, User Manual
Transcript
Appendix B System Signal Variables Introduction Programming Controller Data Topic Page Programming Controller Data 305 I/O Variables 307 The controller supports system variables that you can configure. The system variables are defined as: • SAFE: the controller can use this information in safety-related functions. • NON-SAFE: additional information that safety functions must not rely on. These are the system variables. System Variable Unit/Value Read/Write Description(1) Contact Assembly 1 Contact Assembly 2 Contact Assembly 3 Contact Assembly 4 true false Write On true, the contact closes; on false the contact does not close. Only available for a GuardPLC 2000 controller. [BOOL] NON-SAFE Cooling Fan State 0, 1, 2 Read 0 = normal 1 = fans OK 2 = fan error Only available for a GuardPLC 2000 controller. [BYTE] NON-SAFE Cycle Time milliseconds Read Duration of the last cycle [UDINT] SAFE Date Time Seconds Date Time Milliseconds seconds Read milliseconds Time passed since 1970. An automatic switchover from summer to winter time is not supported. [UDINT] NON-SAFE Emergency Stop 1 Emergency Stop 2 Emergency Stop 3 Emergency Stop 4 true false True triggers Emergency Off [BOOL] SAFE Use these signals to force all inputs and outputs to the zero/OFF state from within the user program. Write Publication 1753-UM001C-EN-P - March 2010 305