Download User Manual
Transcript
Chapter 5—System Configuration and Operation Contactor Feeder Operation Mode The Contactor Feeder operation mode accepts open/close commands to control the contactor in a feeder application. Recommended User Interface Overlays for the Contactor Feeder Operating Mode Figure 137. C445UC-I7: IEC Control and Status A close command will activate Output 1. An open command will de-activate Output 1. C445 Feedback Signal Source Selector parameter. Input source of the feedback signals: ● 0 – No feedback source ● 1 – User interface inputs (In#2 – aux on) ● 2 – Base control inputs (In#2 – aux on) ● 3 – Fieldbus parameter (2nd bit – aux on) Figure 138. C445UC-I8: IEC Control and Status The C445 will issue a control fault when: ● An Open command active and the Aux On feedback input is true. ● Current is detected after an open command. ● A Close command is active and the Aux On feedback input is false. When the C445 experiences a fault/inhibit condition Output 1 will be de-activated to open the feeder. ● Output 1 – feeder contactor coil (NO) ● Outputs 2 and 3 – open for user configuration and their function can be selected by the user. Figure 139. C445UC-N7: NEMA Control and Status Figure 136. Timing Diagram for the Contactor Feeder Operating Mode Timing Diagram Control Fault delay CLOSE Figure 140. C445UC-N8: NEMA Control and Status OPEN 122 Power Xpert C445 Global Motor Management Relay MN042003EN—September 2015 www.eaton.com