Download User Manual
Transcript
Appendix D—Modbus Register Map Table 125. C445 Modbus Register Map, continued Register Name Attribute Description 312 Active Fault UINT16 RO Default: 0 Enum Active Fault 238 Value Description 0 No Faults 1 Under voltage 2 Over voltage 3 External GF 4 Residual GF 5 Current phase loss 6 Current unbalance 7 Instantaneous over current 8 Jam 9 PF Deviation 10 Voltage phase loss 11 Voltage unbalance 12 Frequency deviation fast 13 Frequency deviation slow 14 Under current 15 High power 16 Low power 17 Contactor failure 18 Starts limit exceeded 19 Overload 20 Stall 21 Phase rotation mismatch 22 PTC—See PTC State for details 23 Under voltage restart 24 Measurement Module fault 25 Communication loss on active fieldbus 26 Measurement Module not available or communication loss with the module 27 User Interface not available or communication loss with the module 28 Test trip was triggered 29 Option Card not available or communication loss with the module 30 RTC / Backup Memory Option Board NV memory fail 31 Currently connected User Interface does not match with what was connected before 32 Currently connected Measurement Module does not match with what was connected before 33 Currently connected Option Card does not match with what was connected before 34 Measurement Module firmware is incompatible 35 User Interface firmware is incompatible Power Xpert C445 Global Motor Management Relay MN042003EN—September 2015 www.eaton.com