Download User Manual
Transcript
Appendix D—Modbus Register Map Table 125. C445 Modbus Register Map, continued Register Name Attribute Description 6004 Base Control Module RS485 Modbus Timeout UINT16 RW NV The time before Modbus communications are considered lost. Every valid message received will reset this timer. The timeout is based on milliseconds. When this timer expires, communication loss behavior will be triggered. A value of zero (0) will disable the communication timeout. Default: 2000 Units: ms Config CRC Admin Lock USB Lock Backup Mem 6005 Base Control Module USB Modbus Timeout UINT16 RW NV Default: 10000 The time before Modbus communications are considered lost. Every valid message received will reset this timer. The timeout is based on milliseconds. When this timer expires, communication loss behavior will be triggered. A value of zero (0) will disable the communication timeout. Config CRC Admin Lock USB Lock Backup Mem 6006 User Interface USB Modbus Timeout UINT16 RW NV Default: 0 The time before Modbus communications are considered lost. Every valid message received will reset this timer. The timeout is based on milliseconds. When this timer expires, communication loss behavior will be triggered. A value of zero (0) will disable the communication timeout. Units: ms Backup Mem 6007 Modbus TCP Com Timeout UINT16 RW NV Default: 2000 The time before Modbus TCP communications are considered lost. Every valid message received will reset this timer. The timeout is based on milliseconds. When this timer expires, communication loss behavior will be triggered. A value of zero (0) will disable the communication timeout. Units: ms Config CRC Admin Lock USB Lock 6008 REST Web services Communication Timeout UINT16 RW NV Default: 0 Units: ms The time before HTTP REST communications are considered lost. Every valid poll assembly message received will reset this timer. The timeout is based on milliseconds. When this timer expires, communication loss behavior will be triggered. A value of zero (0) will disable the communication timeout. Config CRC Admin Lock USB Lock 6010 6012 6014 Present Ethernet IP Address UINT8 RO The Active IP Address Being used on the Network. Array size: 4 Array of 2 registers Present Ethernet Subnet Mask UINT8 RO The Active Subnet Mask IP Address Being used on the Network. Array size: 4 Array of 2 registers Present Ethernet Default Gateway UINT8 RO The Active Default Gateway IP Address Being used on the Network. Array size: 4 Array of 2 registers Power Xpert C445 Global Motor Management Relay MN042003EN—September 2015 www.eaton.com 307