Appendix D—Modbus Register Map
Table 125. C445 Modbus Register Map, continued
Register
Name
Attribute
Description
6004
Base Control Module
RS485 Modbus
Timeout
UINT16 RW NV
The time before Modbus communications are considered lost. Every valid message received will
reset this timer. The timeout is based on milliseconds. When this timer expires, communication loss
behavior will be triggered. A value of zero (0) will disable the communication timeout.
Default: 2000
Units: ms
Config CRC
Admin Lock
USB Lock
Backup Mem
6005
Base Control Module
USB Modbus
Timeout
UINT16 RW NV
Default: 10000
The time before Modbus communications are considered lost. Every valid message received will
reset this timer. The timeout is based on milliseconds. When this timer expires, communication loss
behavior will be triggered. A value of zero (0) will disable the communication timeout.
Config CRC
Admin Lock
USB Lock
Backup Mem
6006
User Interface USB
Modbus Timeout
UINT16 RW NV
Default: 0
The time before Modbus communications are considered lost. Every valid message received will
reset this timer. The timeout is based on milliseconds. When this timer expires, communication loss
behavior will be triggered. A value of zero (0) will disable the communication timeout.
Units: ms
Backup Mem
6007
Modbus TCP Com
Timeout
UINT16 RW NV
Default: 2000
The time before Modbus TCP communications are considered lost. Every valid message received
will reset this timer. The timeout is based on milliseconds. When this timer expires, communication
loss behavior will be triggered. A value of zero (0) will disable the communication timeout.
Units: ms
Config CRC
Admin Lock
USB Lock
6008
REST Web services
Communication
Timeout
UINT16 RW NV
Default: 0
Units: ms
The time before HTTP REST communications are considered lost. Every valid poll assembly message
received will reset this timer. The timeout is based on milliseconds. When this timer expires,
communication loss behavior will be triggered. A value of zero (0) will disable the communication
timeout.
Config CRC
Admin Lock
USB Lock
6010
6012
6014
Present Ethernet IP
Address
UINT8 RO
The Active IP Address Being used on the Network.
Array size: 4
Array of 2 registers
Present Ethernet
Subnet Mask
UINT8 RO
The Active Subnet Mask IP Address Being used on the Network.
Array size: 4
Array of 2 registers
Present Ethernet
Default Gateway
UINT8 RO
The Active Default Gateway IP Address Being used on the Network.
Array size: 4
Array of 2 registers