Download Display - Siemens
Transcript
Driver Blocks Table 3-20 Assignment of the accompanying values to the block parameters Accompanying value Block parameter 1 BGNR 2 KNR Operating and Monitoring via OS For this driver block no allocated display block is necessary in the OS. Instead of this the elements of the standard grafic library of WinCC can be used for display. I/O Bars The following tables present the input and output bars of the block. Table 3-21 Input bar Meaning Element Type Initial value Attr. O & M Permitted values XE Upper range limit REAL 100,0 Q XA Lower range limit REAL 0,0 Q SIMON Simulation ON BOOL 0 Q SIM_V Simulation value REAL 0,0 Q BGNR Module number INT –1 0...60, 100...160 KNR Channel number on module (with mode) INT 0 0...31, 32...63, 100...131, 200...231 EN_MSG Enable control system messages BOOL 0 Q EV_ID Message number DWORD 0 U Type Initial value Attr. Table 3-22 Output bar Element Meaning X Analog value REAL 0,0 XF Analog signal disturbed 1) BOOL 1 BGF Module defective (QCOM v QVZ v EANK v KF) BOOL 1 QPARF Parameter assignment error 2) BOOL 0 STATUS Block state WORD 0 U QERR Inverted value of ENO BOOL 1 U 1) 2) O & M Permitted values XF = 0 if SIMON = 1 If QPARF = 1 no processing of the block is done. 3-24 Library of Driver Blocks C79000-G8076-C711-04