Transcript
Driver Blocks S Fault processing The following outputs are set for fault detection: BGF Module fault (Hardware) Reaction: Execution is aborted, S 305 STOE Module failure (Software) – Self-detection by interface module – Monitoring has responded Reaction: Execution is aborted PAF1, PAF2 The partner connected to channel 1 or channel 2 respectively is defective (USART fault at interface 1/2, e.g. incorrect baud rate, parity, frame or overrun error). Reaction: None KF1, KF2 There is a fault in the link between partner 1/2 and the interface module (line fault at interface 1/2, e.g. character time-out 220ms, acknowledgement time-out 550 ms, return message time-out 5 s, checksum error BCC 3964R after 5 repetitions, open-circuit). Reaction: S387 STF Configuration fault – Target block cannot be found – Target block too short Reaction: Message frame is rejected, processing aborted. The no. of the errouneous DB (without base) can be read at output ”FBST”. EPU Receive buffer overflow Reaction: Execution is continued. The last message is rejected by the interface module if buffer processing does not continue after a waiting time. Remedy: Check processing cycle Note: KF and PAF are not set in message-specific manner, they are indicated in all drivers accessing the module during the error bit output (no error interpretation related to the transmitter block). 3-122 Library of Driver Blocks C79000-G8076-C711-04