Download Display - Siemens
Transcript
Driver Blocks Error handling During processing the driver monitors both the hardware and the values. This results in the following error displays: S QPARF = 1: Parameter assignment error (see startup characteristics) S BGF = 1: This output indicates the module or the process values are not available. Possible causes: QVZ: Module time-out (incorrect address, incorrect jumpers or module is defective), EANK:multiple addressing/acknowledge from modules (incorrect jumper setting) S ENO = 0: The operating system has recognized a general error by itself (e.g. overflow). Startup Characteristics During a startup/initial run or parameter change all parameters are checked for permitted values. If the allowed limits are exceeded, the driver sets its output QPARF = 1 and does not carry out any further processing in the subsequent cycles, e.g. no I/O accesses are done and the outputs retain their old values. Time Response Does not exist. If the driver output values are needed from blocks with time response (e.g. closed-loop control block) the driver has to be installed in the same OB before this block. Message Behavior Description of the message behavior. The PCS 7 block ALARM_8P is used to generate control-system messages. Table 3-100 Message No. Control-system messages of the TM_RZA block Block parameter Initial start message text 1 QPARF Parameter assignment error 2 QCOM Communication error FM 3 QVZ Module time-out (S305) S 4 EANK Multiple addressing (S313) S Table 3-101 (F410) S S Assignment of the accompanying values to the block parameters Accompanying value 3-118 Message class Block parameter 1 BGNR 2 KNR Library of Driver Blocks C79000-G8076-C711-04