Download PLC Connection Manual
Transcript
App4-2 Appendix 4 1 : n Connection (Multi-drop) Wiring (RS-422/485) For connecting information, refer to the instruction manual for the PLC. Example: The following example shows how one V7 series is connected to three PLCs made by MITSUBISHI. For more information, refer to MITSUBISHI’s instruction manual for the PLC. V706 V Series MJ2*2 CN1 Link unit Link unit Signal Pin No. Pin No. Name Signal Name Signal Name Signal Name *1 SHELL 1 FG FG FG SG 5 7 SG SG SG +SD 1 12 RDA RDA RDA -SD 2 13 RDB RDB RDB +RD 7 24 SDA SDA SDA -RD 8 25 SDB SDB SDB Terminating resistance (OFF) Terminating resistance (OFF) Terminating resistance (ON) RD terminating resistance (ON) *1 Pin No. 1 of CN1 is used as FG. The metal shell of the modular jack 2 on the V706 is used as SG. *2 Slide the slide switch on the V706 to the lower position for RS-422. Link unit * Use shielded twist-pair cables. V-SFT Setting The following settings must be made on the V-SFT editor. Only the points different from those described in “V-SFT Setting (1 : 1 Connection)” (page 1-10) are explained here. PLC Selection Select the PLC that is connected. Check that the PLC to be connected is ready for 1 : n connection. Refer to the “Appendix.” • Setting Procedure [System Setting] → [PLC Communication] → [PLC Model] dialog Communication Parameter Setting • Setting Procedure [System Setting] → [PLC Communication] → [Communication Parameters] dialog • Setting Items Select “1 : n” for [Connection]. PLC Port Setting Set the port number of each PLC not in the [Communication Parameters] dialog but in the [Memory Setting] dialog for each part.