Download SuperCombi®

Transcript
OH
Heatsink Max Temp.
‘Udc-ripple’
Volt Ripple Exceeds
‘
‘Udc-OV’
Battery over voltage.
’: blink
Udc-OV
Battery over voltage.
‘Idc-OC’
Over current.
‘
Place the “SuperCombi®”
in a cool and
well-ventilated room, or
reduce the load.
Voltage ripple on the DC
input exceeds 1.25Vrms
Check the battery cables
and terminals.
Check the battery capacity;
increase it if necessary.
’: blink
Udc-ripple
Volt Ripple Exceeds
‘
The ambient temperature is
too high, or the load is
excessive.
’: blink
Idc-OC
Over current.
Install batteries with a
The INVERTER of
higher capacity.
“SuperCombi®” cuts out as Use shorter and/or thicker
a result of excessive voltage battery cables and reset the
ripple on the DC input
SuperCombi® (Power OFF
and ON again).
Battery charger is not in
normal charging status to
cause battery voltage too
high.
“SuperCombi®” will need
to be sent to service for
repair.
Incorrect battery voltage
connection (12V system but Recheck if the
connected to 24V battery)
SuperCombi® and the
battery voltage is matched.
The actual charge current is
1.5 times larger than the set
current value (D1-08) when
AC CHARGER is
operating.
Stop the Charge mode of
the “SuperCombi®”.
“SuperCombi®” will need
to be sent to service for
repair.
Rich Electric Co. SuperCombi® Quick Reference Guide V7.19 Copyright 2009