Download wiSTAR Occupancy Sensor - Wall Mounted Install Instructions

Transcript
Installation Guide
Model: WIS-OSW
Hubbell Building Automation
Occupancy Sensor - Wall Mounted
Specifications
1.1”
2.5”
28mm
64mm
Power Supply
Indoor light energy harvesting
Optional: Supplemental battery or
2-wire connector for external power
or remote solar cell (3-5 VDC)
RF Communications
Solar Cell
5.8”
148mm
EnOcean 902 MHz
RF Transmission Range
80 ft. (25 m)
Motion Sensing Range
Up to 100 ft. (25 m)
(refer to coverage diagrams)
Minimum Operating Light
50 lux (for auto-off only)
Startup Charge Times*
(from empty)
Linking only
4 minutes @ 100 lux
1.5 minutes @ 200 lux
Lens
Motion Transmission
6 minutes @ 100 lux
3.5 minutes @ 200 lux
Button
Interface
Package Contents
▪ Occupancy Sensor
▪ 2 screws, 2 wall anchors
▪ 1 wide angle lens
(installed)
▪ 1 long range lens
Light/Walk Test Modes
5.5 hours @ 200 lux
1.8”
45.7mm
Tools Required
▪
▪
▪
▪
▪
Power drill, 3/16” bit
Screwdriver
Leveling tool
Light meter
Battery (CR2032) for testing
Time to Full Charge*
Sustaining Charge Time
Motion Transmission
Interval
3 hours per 24 hours @ 200 lux
Variable 60 - 300 seconds
(based on real-time charge rate)
60 sec @ 200 lux - 300 sec @ 50 lux
Heartbeat Transmission
Interval
Variable 120 - 600 seconds
(based on real-time charge rate)
120 sec @ 200 lux - 600 sec @ 50 lux
+ 0-50 sec randomized delay
Product Description
Operating Life in
Total Darkness
The wall-mounted Occupancy Sensor saves energy and adds
convenience by accurately detecting when an area is occupied
or vacant.
EEP (EnOcean
Equipment Profile)
It is wireless, solar-powered, and uses a passive infrared (PIR)
sensor to detect motion. The occupancy sensor transmits RF
signals to control lighting, HVAC and outlets more efficiently.
Dimensions
Weight
Features Include:
Mounting Height
▪ Sends wireless signals to receiving devices when
Environment
motion is detected
Mounts flush on the wall or in a corner
Interchangeable lenses for tailored sensor coverage
A5-07-02
5.83” L x 2.52” W x 1.8” D
(148 mm x 64 mm x 45.7 mm)
4.09 oz. (116 g)
6-8’ (recommended)
Indoor use only
20% to 95% relative humidity
(non-condensing)
communications
Works with other sensors for enhanced occupancy tracking
48 hours
(after full charge)
14° to 104°F (-10° to 40°C)
▪ Harvests indoor light to power the sensor and wireless
▪
▪
▪
▪
▪
9 hours @ 200 lux
Agency Compliance
FCC, IC, RoHS
* Sunlight, bright lighting or a battery can be temporarily used
to significantly shorten startup charge times.
Built-in tests to confirm operation at installed location
Supplemental battery or alternative power supply options for
extreme low-light conditions
▪
© 2013 Hubbell Building Automation
|
www.hubbell-automation.com
Page 1
Occupancy Sensor – Wall Mounted • Installation Guide
Functional Description
Long Range Coverage
If occupation is detected by the permanently active PIR sensor,
a radio telegram indicating the occupied status will transmit
immediately. A motion transmission interval timer starts to run
with a variable timer length varying between 60 and 300 seconds, depending on the light level. No radio telegrams will be
sent out until the timer expires.
After the timer has expired, the unit will transmit again if occupancy was detected during the timer interval period. If occupancy was not detected, the unit will transmit a heartbeat signal
- sending the unoccupied heartbeat status message every 2 - 11
minutes (depending on the light level).
Planning
Take a moment to plan for the sensor’s successful operation and
optimal communication with other system components.
Remove the sensor from its packaging and place it under a
bright light to provide the required startup charge. Optionally,
to ensure the sensor energy storage is fully charged, insert a
CR2032 battery for 5 minutes while in a well-lit location.
▪ Ensure the location provides consistent and adequate light
▪ Install with the appropriate lens for the required coverage
▪ Locate the sensor between 6 and 8 ft (1.8 to 2.4 m) high with
an unobstructed view of the space
77°
16 ft
8 ft
Top View
21.5°
14°
6.5°
27°
center line
0
8 ft
16 ft
Side View
6.8 ft
(2.1 m)
3 ft
(1 m)
7 ft
10 ft
(2.2 m) (3 m)
35 ft
(10.7 m)
Installing
60 ft
(18.3 m)
100 ft
(30.5 m)
estimated time: 20 minutes
The mounting plate can be installed flush to the wall or angled
in a corner.
NOTE: It is often easier to link the sensor before it is mounted
on the wall. Refer to the Linking section.
1. Remove the mounting plate from the sensor assembly by
pressing the release tab located on the top of the sensor.
2. Decide which of the two installation options is appropriate:
A. Flush to the Wall
i.
▪ For wide angle coverage, locate the sensor where traffic
moves across the detection pattern, not in and out
▪ Consider the area’s traffic patterns and principal use, for
example, walking, lounging or sleeping
Orient the mounting plate
using the pencil marks.
Mark the two mounting
screw drill points.
▪ Provide a minimum clearance of 4 ft. (1.2 m) away from heat
ii. Drill two holes with a 3/16”
bit and insert wall anchors.
▪ Consider the construction materials (such as metal) in the
iii. Insert the first screw
loosely and level the mounting plate.
sources, light bulbs, forced air, or ventilation systems
space and obstacles that may interfere with RF signals
Sensor Range
A single occupancy sensor provides sufficient coverage for most
applications. For some applications, multiple sensors may be
required to provide complete coverage.
iv. Insert the 2nd screw then hand-tighten the 1st screw.
B. Angled in a Corner
i.
Orient the mounting plate
using the pencil marks.
ii. Carefully drill through two of
the four blind holes on the
angled sides of the mounting
plate (one on each side).
Wide Angle Coverage
33 ft (10 m)
Top View
iii. Mark the two mounting screw
drill points and drill two pilot holes with a 3/16”
drill bit and insert the wall anchors.
16 ft (5 m)
iv. Insert the two screws and hand-tighten them.
0
3. Fit the sensor into the groove at the bottom of the mounting
p
p
plate
and close the top.
16 ft (5 m)
33 ft (10 m)
Side View
6.8 ft
(2.1 m)
6 ft
15 ft
25 ft
50 ft
© 2013 Hubbell Building Automation
|
www.hubbell-automation.com
Page 2
Occupancy Sensor – Wall Mounted • Installation Guide
The sensor snaps into the tab at the top.
test button is pressed indicates insufficient charge.
If a battery is used to charge the sensor for a light test, ensure it
is removed to get an accurate light measurement.
A test mode will stay active for 3 minutes. To exit a test and
resume normal operation, press and hold the Menu button for 5
seconds.
Walk Test
4. Confirm the sensor is properly positioned
d tto d
detect
t t motion
ti
and has sufficient light to operate, see the See Walk Test and
See Light Test sections.
Linking
Two or more compatible devices can be linked and configured
to provide the desired control. There are two basic types of
devices in the system; transmitters and transceivers.
▪ Transmit-only: Transmitters are simple energy-harvesting
devices that send RF messages to communicate a condition,
level, or state. Transmitters can only be linked to transceivers.
Examples > Self-powered Light Switches, Occupancy Sensors
▪ Transmit & Receive: Transceivers are controlling devices
that send as well as receive RF messages. They also process
relevant control logic, and actuate the appropriate outputs
(switching a light on or off for example). Transceivers can be
linked with transmitters as well as other transceivers. A transceiver can have up to 30 devices linked to it.
Examples > Relays, Gateways
The Occupancy Sensor is a Transmit-only Device.
To link the sensor to a transceiver; the transceiver must first be
powered, within wireless range, and set to accepts links.
Next, the desired transmitter, or another transceiver, is triggered
to send a special link message. The awaiting transceiver receives
and stores the link permanently so the devices can interact to
provide a variety of intelligent control options.
To Link or Unlink an Occupancy Sensor
Use the walk test to confirm motion is within the sensor’s range.
1. Press and hold the Set button for 5 seconds.
••> Red LED will blink to confirm that a walk test is active.
2. Move in and out of the sensor‘s range to determine its coverage area.
••> Sensor will blink when it detects motion.
3. Make small hand movements just inside the limit of the sensor‘s range to see if the motion triggers a response.
NOTE: Ensure the sensor does not falsely trigger from user
activity outside the desired zone or other heat and motion
sources. If false triggering occurs, adjust the sensitivity switch
(next to the battery slot) from REG to LOW.
Light Test
Use the light test to measure real-time light levels and confirm
whether the occupancy sensor has sufficient light.
1. Create a realistic lighting condition (the test measures the
real-time light level).
2. Press and hold the Set button for 10 seconds.
••> Red & green LEDs will blink to confirm light test is active.
3. Watch the LED blink rate to determine the light strength.
••> The highest is 5 blinks which indicates very good light
(200 lux or more). 1 blink indicates minimum light (<25 lux).
NOTE: If there is no blink rate, consider relocating the sensor or
installing a battery to provide supplemental power.
Changing the Lens
1. Set the desired transceiver to the
desired Link/Unlink mode (refer
to that device’s installation guide).
The Occupancy Sensor package contains two lenses: a wide
angle lens and a long range lens. The wide angle lens is installed
by default and can be distinguished from the long range lens by
the pattern.
2. Click the Menu button on the
bottom of the sensor once. This
sends a link/unlink radio
telegram.
NOTE: Ensure smooth side of lens faces out.
Lens Patterns
NOTE: The button interface on the sensor is used for linking
and testing only. The occupancy timer settings are configured on the transceiver to which the sensor is linked.
Wide
de Angle
g e Lens
e
Long
g Range
g Lens
Refer to the “Linking” section of the transceiver/controller
installation guides to complete the linking & setup process.
Testing the Sensor
Before starting a test, ensure the sensor’s energy storage is fully
charged by placing it under bright light (at least 500 lux) for 20
minutes, or insert a battery for 5 minutes while in a well-lit area.
NOTE: If the sensor does not have a sufficient charge, it cannot
enter into the test modes. No LED light or 1 red blink when the
© 2013 Hubbell Building Automation
|
www.hubbell-automation.com
Page 3
Occupancy Sensor – Wall Mounted • Installation Guide
Troubleshooting
To change the lens:
1. If the sensor is mounted, press the top tab and remove it
from the mounting plate.
2. Unscrew the small screw on the back at the bottom and
remove the front cover.
Problem
Sensor does not
generate a wireless
message
Sensor is activated
when there is nothing to detect
Linked device does
not respond to
wireless messages
Solution Checklist
▪
▪
▪
▪
▪
▪
▪
▪
3. Remove the installed lens by
gently squeezing it to ease one
side out of its groove, and then
the other.
Explanation of
Occupied & Heartbeat Message Data
Telegrams
4. Insert the lens you want to use
by aligning the notch with the
top on the front cover. Orient the
smooth side facing out, and the
textured side facing the sensor.
Verify the LED blinks when motion is detected
during a walk test
Verify the solar cell is charged properly
Verify there is 4 ft. (1.2 m) clearance from heat
sources that may disturb sensing
Reduce sensitivity setting by moving the PIR
sensitivity switch on the back from REG to
LOW (the left-hand position)
Check for environment or range issues
Verify the device is linked
Check the transceiver connection and the wiring for errors
Check if appropriate devices are linked according to good system planning
Data Byte 3: Super Capacitor Voltage, 0-255 (% of 0-4.5V)
Data Byte 2: Solar Panel Current, 0-127 uA
Data Byte 1: 0xFF (occupied) or 0x00 (unoccupied)
Data Byte 0: 0x0F
902 MHz: FCC: SZV-EOSW05
IC: 5713-EOSW05
5. Hold both edges of the lens, flex it gently and push until it
pops into the grooves. Make sure the edges are flush.
NOTE: If the lens is out of
position, the sensor will not
detect activity properly.
6. Replace the top edge of the
front cover and then close it
on the sensor.
This device complies with part 15 of the FCC rules and Industry Canada ICES-003.
Operation is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
IMPORTANT! Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils
radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes:
(1) l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit
accepter tout brouillage radioélectrique subi, meme si le brouillage est susceptible d’en
compromettre le fonctionnement.
IMPORTANT! Tous les changements ou modifications pas expressément approuvés
par la partie responsable de la conformité ont pu vider l’autorité de l’utilisateur pour
actioner cet équipment.
Limited Warranty
7. Replace the bottom screw
and remount sensor on the plate.
ONE YEAR
Installing Supplemental Battery (optional)
If light levels are very low where the sensor is installed, auxiliary
battery power (CR2032) can be used to supplement the solar
energy harvester.
1. Remove the sensor from the
mounting plate.
2. Unsnap sensor cover and
identify the battery holder
on the circuit board.
3. Insert the battery under the
clip with the positive pole (+)
up and press it in place.
4. Replace cover and remount
the sensor on the wall.
© 2013 Hubbell Building Automation
|
www.hubbell-automation.com
Page 4
XOSWIGPLA