Download LACCD IT Design Standards
Transcript
LACCD IT Design Standards 2009 With the complete loss of the digital and analog network communications, all UPS modules shall have the capability to support the critical load up to their rated load; however capability to switch modes to static bypass will be inhibited. With the complete loss of one or both of the UPS conmunication networks, each UPS module shall have the capability to detect an internal failure and remove itself from the paralleled UPS bus. Control in this method eliminates the need for system wide synchronization control signals, therefore eliminating any possibility of a synchronization control failure causing the entire system to go off line or remove power from the critical load. It shall not be possible for a failure in the controls of one UPS power module to propagate a failure into other UPS power modules. Front Panel Display: The UPS shall include a front panel display consisting of a graphical LCD display with backlight, four status LED’s, and a four-key keypad. The LCD shall display a mimic screen of power flow through the UPS system when programmed for this function. The keypad keys shall be menu driven per the function being performed. Graphical LCD display: Includes basic language (English and local selectable languages), display of unit function and operating parameters. It shall be used to signify the operating state of the UPS, for indicating alarms, for changing operations control parameters and set points. The graphical display shall have a real time clock which will stamp events with event type and time information, reviewable in the logged data menus. Local language packages available: English, Spanish, French, German, Portuguese (Standard) English, Finnish, Norwegian, Swedish, Russian English, Hungarian, Polish, Romanian, Czech, Danish English, Greek, Turkish, Bulgarian English, Korean English, Chinese Four status LED’s, which indicate: Alarms, with a red LED On Battery, with a yellow LED On Bypass, with a yellow LED Enterprise Data Center Design – Std 003-0909 Page 36