3 SPECIFICATIONS MELSEC-Q 3) Channel related trouble information When a module type slave station, this area stores the trouble information for each module that is outputting an error. This area does not have a header and stores this information at the end of the identifier related trouble information. Each channel trouble information consists of an identifier No., channel No., and error type of 3 bytes. (End of identifier area) Buffer memory 1st byte: Identifier No. (2nd byte) channel No.1 (1st byte) identifier No.1 (4th byte) identifier No.2 (3rd byte) trouble type 1 (6th byte) trouble type 2 (5th byte) channel No.2 LSB MSB 7 Bit position 6 5 4 3 2 1 0 Identifier Nos. 0 to 63 bits 6 and 7 are set to 10. 2nd byte: Channel No. LSB MSB Bit position 7 6 5 4 3 2 1 0 Input/output 00 = Reserved 01 = Input 10 = Output 11 = Input/output Channel number 0 to 63 3rd byte: Trouble type LSB MSB Bit position 7 6 5 Channel type 000 = Reserved 001 = Bit 010 = 2 bit 011 = 4 bit 100 = byte 101 = Word 110 = 2 words 111 = Reserved 3 - 38 4 3 2 1 0 Error type: 0 Reserved 1 Short circuit 2 Voltage too low 3 Voltage too high 4 Overload 5 Temperature too high 6 Disconnected wire 7 Upper limit exceeded 8 Lower limit exceeded 9 Error 10 Reserved 15 Reserved 16 Manufacturer 31 Manufacturer 3 - 38