Transcript
Sunny Boy 2000 Technical Description Blinking code 7: Drastic Differential Current change The yellow failure indication LED is activated for 5 seconds, out for 3 seconds and then blinks seven times. The code is sent three times. If the failure persists the indication is repeated. The Sunny Boy´s monitoring systems have detected a differential current and immediately disconnected the device from the grid. The integrated all-pole sensitive differential current control monitors the discharge current between the AC output of the inverter and the PV-panel. This additional safety feature is triggered by drastic changes of the differential current of I∆N ≥ 30 mA and disconnects the inverter from the grid within 0.2 seconds. SB2000-11:EE - 47 - SMA Regelsysteme GmbH