PROFINET Operating Behavior
PROFINET alarms using the example of MOVIDRIVE® B
I
6
0
A unit error of the MOVIDRIVE® B or the integrated switch results in a diagnostics alarm
being sent to the SIMATIC control as a so-called "incoming event". The "SF" LED lights
up red. You can determine the cause of the error in STEP 7 HWKONFIG. Go to ONLINE, mark the symbol of the DFE32B and check the module information via the context
menu (right mouse button).
58647AXX
Manual – DFE32B PROFINET IO Fieldbus Interface
63