Download 3 - SEW-EURODRIVE
Transcript
Configuration via PROFIdrive Data Set 47 Structure of the PROFINET parameter channel I 7 0 7.2.1 Parameter setting procedure via data set 47 Parameter access takes place with the combination of the WRITE RECORD and READ RECORD PROFINET services. The parameter setting order is transferred to the IO device using the WRITE.req, whereupon it is processed internally. The controller now sends a READ.req to pick up the parameter setting response. The device sends a positive response READ.res. The user data now contain the parameter setting response of the parameter setting order that was previously sent with WRITE.req (see the following figure). This mechanism applies to a PROFINET controller. Controller Parameter Request PROFINET SEW-Device WRITE.req DS47 with data (parameter request) Parameter Request WRITE.res without data READ.req DS47 without data Parameter Response READ.res(+) with data (parameter response) Figure 4: Telegram sequence for parameter access via Read/Write Record Manual – DFE32B PROFINET IO Fieldbus Interface Parameter Processing Parameter Response 62208AXX 67