Download User manual
Transcript
D9ed2-FE-uso 20-01-2006 14:58 Pagina 7 Table of standard parameters If not specified, each the parameter must be doubled: one set for LOOP1 and one set for LOOP2. If the parameter is unique (1 parameter for both the loops) it is pointed out in the notes column Configuration Mnemonic code IL Prot baud PStr Unit Sc.dd Sc.Hi Sc.Lo Parameter descritption Digital input function IL Communication protocol Baud rate Instrument position Engineering unit N° of decimals Low range High range Setting range Unit see table 1 M.bus/Jbus 1200, 2400, 4800, 9600 baud Alone/left side/central/right side see table 2 0...3 -999...9999 Engineering unit -999...9999 Engineering unit Alarms and auxiliary Mnemonic code A1hy A1SR A1.tp A1Lb A1.O t.Fil In.Sh Addr Hi.PV OP.lk Ack Nt.O1 RF.L RF.H RF Parameter descritption AL1 hysteresis AL1 alarm source AL1 alarm type Latching/blocking alarm functions AL1 output Filter time constant Input shift Communications address PV (measure) Hold Output lock Alarms acknowledge Negate (NOT) OP1 RF low range RF high range Reference value Setting range Unit 0.1...10.0 % range Loop 1/loop 2 See table 3 None/Ltch/Bloc/LtbL Internal status/OP1/OP2/OP3/OP4 OFF/1...30 s OFF/-60...+60 Digit 1...247 0/1 0/1 0/1 0/1 low range...RF. H Engineering unit RF. L...high range Engineering unit range Engineering unit Factory setting not used M.bus 9600 Alone none 0 Low range High range Factory setting 0.5 Loop 1 Inhibited None Internal status Inhibited Inhibited 247 0 0 0 0 ---------- Notes Valid for both the channels Linear scales only Range min. 100 digit (linear scales only) Notes The same parameters are available also for AL2, AL3 and AL4 alarms Valid for both the channels Locks the outputs OP1, OP2, OP3, OP4 Valid for both the channels Available also for OP2 - OP3 - OP4 Standard parameters description The parameters shown in the table are divided into groups which work in the same way. Below they will be described as they are listed in the table. Configuration IL Digital input function - Table 1 Parameter decription Not used Loop 1 measure hold Loop 2 measure hold Hold both the measuring loops Output locks Alarms acknowledge unit Setpoint (SP) A1S.P A2S.P A3S.P A4S.P AL1 - AL2 - AL3 - AL4 threshold Alarm occurrences of AL1,AL2,AL3 and OP4. The range of the alarm threshold correspond to the whole span and it is not limited by the SP Setpoint span. Auxiliary parameters A1.tp A2.tp A3.tp A4.tp Value 0 1 2 3 Alarm type The parameter allows to specify how each shoud function. The types of alarm available are: Action Disable Sensor/Loop Break Absolute high Absolute low Engineering units - Table 2 Parameter description °C (Centigrade degrees) °F (Fahrenheit degrees) None mV (millivolt) V (Volt) mA (milliampere) In.Sh Input shift This function shifts the whole PV scale of up to ±60 digits. Parameter description A (Ampere) bar psi Rh pH Addr Controller address The address range is from 1 to 247 and must be unique for each instrument on the communications bus to the supervisor. 2